Plan Review Notes
Plan Review Notes For Permit 09050383
Permit Number 09050383
Review Stop B
Sequence Number 1
Notes
Date Text
2009-06-01 09:09:49RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 3- PRODUCT APPROVALS SUBMITTAL:
 A) SINGLE HUNG WINDOWS FLORIDA PRODUCT APPROVAL FL10190
 SUBMITTED IS FOR 2004 CODE VERSION. NEED 2007 CODE
 VERSION.
 NOTE: NOA 06-1121.14 MAY BE SUBMITTED ALONE.
  
 B) GLASS BLOCK FLORIDA PRODUCT APPROVAL FL1363-R3 IS
 FOR 2004 CODE VERSION. NEED 2007 CODE VERSION. IN
 ADDITION NOA 07-0626.10 SUBMITTED IS FOR SMALL MISSILE
 IMPACT. PRODUCT APPROVAL NEED TO MEET THE REQUIREMENTS
 OF LARGE MISSILE IMPACT AS REQUIRED BY SEC. R301.2.1.2
 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 C) SINGLE OUTSWING DOOR FLORIDA PRODUCT APPROVAL
 FL539-R4 IS FOR 2004 CODE VERSION. NEED 2007 CODE
 VERSION.
 NOTE: NOA 08-0208.07 MAY BE SUBMITTED ALONE.
  
 D) FRENCH DOORS FLORIDA PRODUCT APPROVAL FL6747 IS FOR
 2004 CODE VERSION. NEED 2007 CODE VERSION. IN ADDITION
 NOA 05-1003.09 SUBMITTED EXPIRED ON APRIL 22, 2009.
 NEED CURRENT NOA.
  
 4- SHEET 1.0:
 A) DEMOLITION PLAN NOTE H REFERS TO "REMOVE EXISTING
 BEAM & ROOF ABOVE" BUT DEMOLITION PLAN SHOWS NOTE H ON
 EXISTING WINDOWS. REVISE/CLARIFY AS REQUIRED TO MATCH.
  
 B) SPECIFY TYPE OF EXISTING WINDOW TO BE REPLACED TO
 VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS OF SEC.
 601.2 OF 2007 FLORIDA EXISTING BUILDING CODE.
  
 5- SHEET 5.0: REVISE THICKNESS OF STUCCO FINISH ON
 DETAIL 1/5.0. MIN. THICKNESS IS 7/8" AS REQUIRED BY
 TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE.
  
 6- SHEET 10.0:
 A) EXTERIOR GLAZED OPENINGS NOTE IS REFERENCING 2004
 FBC. NEED TO REFERENCE THE 2007 FLORIDA RESIDENTIAL
 CODE WHICH IS THE CURRENT CODE.
  
 B) REVISE CORNER DISTANCE A DIMENSION. SEE FIGURE
 R301.2(7) AND FIGURE R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 (561)805-6712