| Plan Review Notes For Permit 09050371 |
| Permit Number |
09050371 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-07-08 21:35:31 | APPROVED WITH PROVISO: PURSANT TO PRIOR REQUEST, IT | | | STILL APPEARS THAT INADEQUATE ESSENTIAL ELECTRICAL | | | SYSTEM TASK LIGHTING HAS BEEN PROVIDED IN THE EXAM | | | ROOMS TO PROVIDE FOR THE ORDERLY CESSATION OF | | | PROCEDURES IN THE EVENT OF A POWER FAILURE AT THE | | | FACILITY. ALTHOUGH SOME EMERGENCY TASK LIGHTING HAS | | | BEEN PROVIDED, A SIGNIFICANT NUMBER OF EXAM ROOMS HAVE | | | BEEN OMMITED. PLEASE PROVIDE A REVISION WHICH SATISFIES | | | THE REQUIREMENTS OF NEC SECTION 517.33. NOTE: BATTERY | | | BACKUP EMERGENCY LIGHTS MAY BE UTILIZED. |
|