| Plan Review Notes For Permit 09050371 |
| Permit Number |
09050371 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-02 16:13:20 | *****DENIED***** | | | | | | 1. PROVIDE A POINT OF COMPASS FOR THE FLOOR PLAN SO AS | | | IT RELATES TO PALM BEACH LAKES BOULEVARD. | | | | | | 2.. ON SHEET A-4, INDICATE FIRE-RATED DOORS. BE ADVISED | | | THAT FIRE-RATED DOORS AND ASSEMBLIES SHALL COMPLY WITH | | | NFPA 80 - 1999 EDITION. | | | | | | 3. ON SHEET E-8, FIRE ALARM NOTES, AMEND NOTE #7 TO | | | INDICATE THAT: DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM. | | | | | | 4. ON SHEET FS-1, UNDER FIRE SPRINKLER NOTES | | | -COMPLIANCE, CODE EDITIONS AS FOLLOWS: NFPA 13 - 2002, | | | NFPA 13R - 2002, NFPA 14 - 2003, NFPA 20 - 2003, AND | | | NFPA 25 - 2002 SHALL BE REFERENCED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EASCH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|