| Plan Review Notes For Permit 09050371 |
| Permit Number |
09050371 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-28 21:12:10 | 1. ESSENTIAL ELECTRICAL SYSTEM TASK LIGHTING DOES NOT | | | APPEAR TO BE INSTALLED IN ALL EXAM AND PROCEDURE AREAS | | | PURSUANT TO THE REQUIREMENTS OF 517.33. | | | 2. THE X RAY DISCONNECTING MEANS APPEARS TO BE LOCATED | | | IN A DIFFERENT ROOM THAN THE X RAY CONTROL PANEL AND IS | | | THEREFORE NOT READILY ACCESSIBLE PURSUANT TO 517.72 (B) | | | 3. SHEET E-1 NOTE 8(B) NON-METALLIC CONDUIT MAY NOT BE | | | RUN UNDERGROUND TO SERVE ANY PATIENT CARE AREAS | | | PURSUANT TO 517.13.(A) AND (B). | | | 4. ALL RECEPTACLES IN PATIENT CARE AREAS SHALL BE | | | DESIGNATED AS HOSPITAL GRADE PURSUANT TO 517.18(B), | | | 5. SHEET E-3.1. NOTE D. PLEASE ENSURE THAT RECEPTACLES | | | IDENTIFIED AS BEING NECESSARY FOR THE ESSENTIAL | | | ELECTRICAL SYSTEM MANDATED FOR THIS FACILITY PURSUANT | | | TO 517.25 ARE PROVIDED IN EACH AREA SO DESIGNATED. IT | | | APPEARS THAT ONLY CERTAIN EXAMINATION AND PROCEDURE | | | ROOMS ARE APPROPRIATELY CIRCUITED. PLEASE CLARIFY. | | | 6. INFORMATIONAL ONLY: SEPARATE APPLICATIONS AND | | | PERMITS ARE REQUIRED FOR THE PROPOSED GENERATOR AND | | | FIRE ALARM SYSTEM. | | | PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS | | | HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I | | | MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT | | | [email protected] |
|