| 2009-06-10 16:11:18 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | FBC-2007 CHAPTER 1 |
| | |
| | A. THE FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT: |
| | |
| | 1. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2007 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | 2. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2007 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | B. A PLUMBING CONTRACTOR SHALL BE REQUIRED TO DO THE |
| | PLUMBING ON THE POTABLE WATER TO THE WATER HEATER & THE |
| | P/T VALVE ETC. SEPARATE PLUMBING PERMIT REQUIRED. FS |
| | 489. |
| | |
| | C. THE VALUATION OF THE WORK APPEARS TO BE LOW: |
| | SECTION 104.6.5 BUILDING PERMIT VALUATION. IF |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, AL- |
| | TERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES |
| | AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| | CLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION FOR BUILDINGS AND |
| | SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| | ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| | (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| | AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| | THE COST OF THE WATER HEATER AND THE OVEN SHALL BE |
| | INCLUDED IN THE VALUE OF THE PROJECT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |