| Notes |
| Date |
Text |
| 2009-06-11 16:03:34 | 2007 FBC | | | INSTALL LP GENERATOR | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE CONCRETE SLAB SUPPORTING THE GENERATOR IS | | | REQUIRED TO BE A MINIMUM OF 3-1/2" THICK. SEE FBC | | | M304.9 | | | | | | 2) THE GENERATOR IS REQUIRED TO BE LOCATED AT LEAST 5 | | | FEET FROM OPENINGS IN WALLS AND AT LEAST 5 FEET FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS PER NFPA 37 SECTION | | | 4.1.4 SHOW COMPLIANCE. FBC M 915.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|