Plan Review Notes
Plan Review Notes For Permit 09050339
Permit Number 09050339
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-11 11:14:53 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE PERMIT CLERK.
  
 2} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING
 GENERATOR AND RELATED EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  