Plan Review Notes
Plan Review Notes For Permit 09050332
Permit Number 09050332
Review Stop P
Sequence Number 1
Notes
Date Text
2009-05-29 16:35:53DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 FBC-2007 CHAPTER 1 (ADMIN)
 MUNICIPAL CODE WPB
  
 1. SUBMIT AN EXISTING FLOOR PLAN TO VERIFY THE EXTENT
 OF ALTERATION. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 2. SHT A1.0 THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 3. SHT A1.0 THE LUNCH ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 4. SHT A1.0. THE SHOWER IS INDICATED AS A NEW SHOWER ON
 SHT PB-1.0. AS A NEW SHOWER IT SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.21 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED). ALSO A TURNING AREA IS REQUIRED
 IN THE SHOWER AREA PER SECTION 11-4.22.3.
  
 5. SUBMIT DETAILS SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS.
 ___FOR TOILET ROOMS
 A. 11-4.22.3 TURNING AREAS
  
 6. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED PER
 SECTION 106.3.5.1.3(3)(8)(10)(13). PLEASE SUBMIT RISER
 SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY
 SECTION 604.9) HATER HAMMER ARRESTORS. SECTION 608.
  
 7. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. BOTH WATER CLOSETS AND THE WASH
 MACHINE ARE NOT VENTED AS SHOWN. SECTION 901.2.1. --
 THE BRANCH TO THE WASH MACHINE SHALL BE 3" PER SECTION
 406.3. -- THE INDIRECT WASTE FOR THE CONDENSATE SHALL
 NOT DRAIN INTO THE SANITARY WASTE DRAIN PER ARTICLE III
 SECTION 90-125(5). CONDENSATE SHALL DRAIN TO SEPARATELY
 OUT THE BUILDING AND CONNECT TO STORM, DRAIN INTO A
 DRYWELL OR INTO A PLANTED AREA. IF CONNECTING TO STORM
 THE CONDENSATE SHALL HAVE A RELIEF VENT (GOOSENECK) AS
 THE DRAIN EXITS THE BUILDING. (SEE RED LINE EXAMPLES OF
 CORRECTIONS FOR THE VENTING ON ONE SET OF PLANS).
  
 8. SUBMIT A DETAIL FOR THE SUSPENDED WATER HEATER.
 INDICATE HOW THE WATER HEATER WILL BE SUPPORTED, WHERE
 THE P/T & PAN DRAIN DISCHARGE LINES TERMINATE, SHOW HOW
 THE THERMAL EXPANSION CONTROL IS ADDRESSED, SHUT OFF
 VALVES ETC. SECTIONS 106.1.2, 504.6,504.7.2, 606.1 &
 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  