| 2009-05-29 16:35:53 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | FBC-2007 CHAPTER 1 (ADMIN) |
| | MUNICIPAL CODE WPB |
| | |
| | 1. SUBMIT AN EXISTING FLOOR PLAN TO VERIFY THE EXTENT |
| | OF ALTERATION. SECTION 106.1.2 (MORE INFORMATION |
| | REQUIRED). |
| | |
| | 2. SHT A1.0 THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE. |
| | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 3. SHT A1.0 THE LUNCH ROOM SINK SHALL BE ACCESSIBLE. |
| | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.24 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). |
| | |
| | 4. SHT A1.0. THE SHOWER IS INDICATED AS A NEW SHOWER ON |
| | SHT PB-1.0. AS A NEW SHOWER IT SHALL BE ACCESSIBLE. |
| | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.21 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE |
| | INFORMATION REQUIRED). ALSO A TURNING AREA IS REQUIRED |
| | IN THE SHOWER AREA PER SECTION 11-4.22.3. |
| | |
| | 5. SUBMIT DETAILS SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. 11-4.16.6 DISPENSERS |
| | ___FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS. |
| | ___FOR TOILET ROOMS |
| | A. 11-4.22.3 TURNING AREAS |
| | |
| | 6. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED PER |
| | SECTION 106.3.5.1.3(3)(8)(10)(13). PLEASE SUBMIT RISER |
| | SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY |
| | SECTION 604.9) HATER HAMMER ARRESTORS. SECTION 608. |
| | |
| | 7. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. BOTH WATER CLOSETS AND THE WASH |
| | MACHINE ARE NOT VENTED AS SHOWN. SECTION 901.2.1. -- |
| | THE BRANCH TO THE WASH MACHINE SHALL BE 3" PER SECTION |
| | 406.3. -- THE INDIRECT WASTE FOR THE CONDENSATE SHALL |
| | NOT DRAIN INTO THE SANITARY WASTE DRAIN PER ARTICLE III |
| | SECTION 90-125(5). CONDENSATE SHALL DRAIN TO SEPARATELY |
| | OUT THE BUILDING AND CONNECT TO STORM, DRAIN INTO A |
| | DRYWELL OR INTO A PLANTED AREA. IF CONNECTING TO STORM |
| | THE CONDENSATE SHALL HAVE A RELIEF VENT (GOOSENECK) AS |
| | THE DRAIN EXITS THE BUILDING. (SEE RED LINE EXAMPLES OF |
| | CORRECTIONS FOR THE VENTING ON ONE SET OF PLANS). |
| | |
| | 8. SUBMIT A DETAIL FOR THE SUSPENDED WATER HEATER. |
| | INDICATE HOW THE WATER HEATER WILL BE SUPPORTED, WHERE |
| | THE P/T & PAN DRAIN DISCHARGE LINES TERMINATE, SHOW HOW |
| | THE THERMAL EXPANSION CONTROL IS ADDRESSED, SHUT OFF |
| | VALVES ETC. SECTIONS 106.1.2, 504.6,504.7.2, 606.1 & |
| | 607.3.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |