| Date |
Text |
| 2009-06-08 14:43:40 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M-1.0: SEVERAL DUCTS ARE MISSING SIZES. ONE SET |
| | OF PLANS HAS BEEN MARKED TO SHOW WHICH SIZES ARE |
| | MISSING. THE 7" ROUND SUPPLY IN EXISTING BATHROOM |
| | WITHIN CLASSROOM #2 IS MISSING CFM DESIGNATION. PLEASE |
| | PROVIDE ALL MISSING INFORMATION IN ACCORDANCE WITH |
| | FBC-M 603.1. |
| | |
| | 2. PAGE M-1.0: DOES THE EXISTING BATHROOM WITHIN |
| | CLASSROOM #2 HAVE AXHAUST AS REQUIRED BY FBC-M TABLE |
| | 403.3? |
| | |
| | 3. PAGE M-1.0: THE VENTILATION SCHEDULE INDICATES THERE |
| | ARE 3 ZONES ON FLOOR PLAN. THERE IS NO INDICATION AS TO |
| | WHERE THESE ZONES ARE LOCATED. ALSO, THE FLOOR PLAN |
| | SHOWS THERE ARE 4 MECHANICAL SYSTEMS AND NOT 3. PLEASE |
| | PROVIDE A VENTILATION CALCULATION WITH SPACE-BY-SPACE |
| | OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, VENTILATION |
| | RATES REQUIRED PER OCCUPANT AND TOTAL VENTILATION |
| | REQUIRED. ALSO PLEASE INDICATE HOW MANY CFM EACH |
| | INDIVIDUAL HVAC SYSTEM WILL PROVIDE TO MEETH THESE |
| | VENTILATION REQUIREMENTS. THIS INFORMATION IS NEEDED TO |
| | DEMONSTRATE COMPLIANCE WITH FBC-EB SECTION 909 FOR |
| | CHANGE OF OCCUPANCY AND FBC-M SECTION 403. |
| | |
| | 4. SHOW BALANCED RETURN FROM BREAKOUT ROOM PER FBC-M |
| | 601.4. |
| | |
| | 5. PAGE A-1.0 SHOWS 1-HOUR FIRE RATED WALLS ON THE |
| | FLOOR PLAN. PAGE M-1.0 SHOWS SEVERAL DUCT PENETRATIONS |
| | OF THESE RATED WALLS. SHOW HOW THESE PENETRATIONS ARE |
| | TO BE PROTECTED IN ACCORDANCE WITH FBC-M 607.5. THE |
| | SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE |
| | AND/OR SMOKE DAMPER SHALL BE SHOWN AND PROPERLY |
| | IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER IN |
| | ACCORDANCE WITH FBC-M 607.8. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |