| Plan Review Notes For Permit 09050332 |
| Permit Number |
09050332 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-16 12:19:17 | ***DENIED*** | | | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006 AS PART OF | | | THE FLORIDA FIRE PREVENTION CODE, 2007 EDITION. | | | | | | 2) IN ADDITION TO SEPARATE SHOP DRAWINGS AND PERMITS, | | | PLEASE PROVIDE THE LAYOUT OF FIRE PROTECTION EQUIPMENT. | | | THE FIRE SPRINKLER LAYOUT MAY BE SHOWN ON THE REFLECTED | | | CEILING PLAN. | | | | | | 3) IS THIS CONSIDERED A FULLY FIRE SPRINKLERED | | | BUILDING? | | | | | | 4) PLEASE PROVIDE A LIFE SAFETY PLAN ILUUSTRATING THE | | | MINIMUM TRAVEL DISTANCES. | | | | | | 5) THE FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR | | | CENTRAL STATION SERVICE IF NOT ALREADY PART OF AN | | | EXISTING SYSTEM. | | | | | | 6) PLEASE PROVIDE THE LOCATIONS OF REQUIRED 2A-10B,C | | | RATED FIRE EXTINGUISHERS. | | | | | | 7) PLEASE PROVIDE THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION OF WALLS AND CEILING. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|