Plan Review Notes
Plan Review Notes For Permit 09050332
Permit Number 09050332
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-16 12:19:17***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006 AS PART OF
 THE FLORIDA FIRE PREVENTION CODE, 2007 EDITION.
  
 2) IN ADDITION TO SEPARATE SHOP DRAWINGS AND PERMITS,
 PLEASE PROVIDE THE LAYOUT OF FIRE PROTECTION EQUIPMENT.
 THE FIRE SPRINKLER LAYOUT MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN.
  
 3) IS THIS CONSIDERED A FULLY FIRE SPRINKLERED
 BUILDING?
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN ILUUSTRATING THE
 MINIMUM TRAVEL DISTANCES.
  
 5) THE FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR
 CENTRAL STATION SERVICE IF NOT ALREADY PART OF AN
 EXISTING SYSTEM.
  
 6) PLEASE PROVIDE THE LOCATIONS OF REQUIRED 2A-10B,C
 RATED FIRE EXTINGUISHERS.
  
 7) PLEASE PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756