| Notes |
| Date |
Text |
| 2009-06-11 14:47:38 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE A PANEL SCHEDULE FOR PANEL "B". | | | | | | 2} LOCATE THE PANELS ON THE PLAN. | | | | | | 3} INDICATE COMPLIANCE WITH CHAPTER 13, SECTION 13-415, | | | ALL THAT APPLY. | | | | | | 4} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE | | | PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|