| 2009-06-02 11:22:41 | BUILDING PLAN REVIEW |
| | PERMIT: 09050332 |
| | ADD: 5841 CORPORATE WAY SUITE# 100 |
| | CONT: LTL BUILDERS, INC. |
| | TEL: (561629-9753 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. PLEASE PROVIDE THE |
| | EXISTING FLOOR PLAN OF THIS SUITE OR LIFE SAFETY PLAN |
| | FOR THE FULL SUITE. 106.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS, COMMERCIAL: |
| | (6) LIFE SAFETY |
| | (7) MEANS OF EGRESS & SPECIFIC OCCUPANCY REQUIREMENTS |
| | PLEASE INCLUDE THE COMMON CORRIDORS OR HALLWAYS, |
| | 1028.1.2 EXTERIOR CORRIDORS, THE MINIMUM CLEAR WIDTH OF |
| | SUCH CORRIDORS SHALL BE SUFFICIENT TO ACCOMMODATE THE |
| | OCCUPANT LOAD BUT SHALL IN NO CASE BE LESS THAN 6 FEET. |
| | THE CORRIDOR TO TTHE LEFT OF THE CLSSROOMS IS TO BE |
| | CONSIDERED AN EXTERIOR CORRIDOR. THE CORRIDOR DIRECTLY |
| | IN FRONT OF THE MAIN ENTRY AND CLASSROOM # 3 CAN'T BE |
| | DERTERMINED AT THIS TIME. |
| | |
| | THE SECOND ISSUE WITH THE CORRIDORS THAT SERVE THE |
| | EDUCATIONAL OCCUPANCY IS THE FIRE RATING OF THE |
| | CORRIDOR. TABLE 1017.1 REQUIRES THE CORRIDOR TO BE A 1 |
| | HOUR RATING FOR BUILDINGS THAT ARE NOT FIRE |
| | SPRINKLERED, AND A EDUCATIONAL OCCUPANCY GREATER THAN |
| | 30. PLANS INDICATE ONLY THE EDUCATIONAL OR CLASS ROOM |
| | ARE TO BE FIRE SPRINKLERED FROM THE NOTE# 3 OF SHEET |
| | A-1.0. AGAIN PLEASE PROVIDE CORRIDOR RATING S OUTSIDE |
| | OF THE TENANT UNIT. |
| | |
| | 2) SHEET A-0.0 INDICATES THAT THE BUILDING TYPE TO BE A |
| | III-A, SPRINKLED: |
| | 2A) IS THE TOTAL BUILDING SPRINKLERED? |
| | 2B) THIS BUILDING TYPE IS INDICATED AS A TYPE IIIA IS |
| | THE BAR JOIST 1 HR PROTECTED? IT APPEARS THIS BUILDING |
| | COULD BE CLASSIFIED AS A III-B WITH AREA MODIFICATIONS |
| | 506.1 & 506.2. |
| | |
| | 3) SHEET A-1.0 INDICATES TWO DOORS IN SERIES LEADING |
| | FROM THE RECEPTION ROOM TO THE LUNCH ROOM, PLEASE |
| | REVIEW SECTION 11-4.13.7 AND FIGURE 26, TWO DOORS IN |
| | SERIES. |
| | |
| | 4) SHEET A-1.0 THE SAME TWO DOORS ON THE LATCH SIDE |
| | WILL REQUIRE 18" CLEAR FOR MANEUVERING CLEARENCES. |
| | 11-4.13.6. |
| | |
| | 5) THE B. O. DOUG WISE WILL DETERMINE IF THE EXISTING |
| | SHOWER WILL REQUIRE ACCESSIBILITY, SINCE THIS IS TO BE |
| | USED AS A TEACHING TOOL. 11-4.21. SHOWER STALL |
| | REQUIREMENTS. |
| | MR. WISE HAS BEEN IN CONTACT WITH MR. TYLKA ALREADY FOR |
| | THIS PROJECT. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |