2009-06-02 11:22:41BUILDING PLAN REVIEW
 PERMIT: 09050332
 ADD: 5841 CORPORATE WAY SUITE# 100
 CONT: LTL BUILDERS, INC.
 TEL: (561629-9753
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. PLEASE PROVIDE THE
 EXISTING FLOOR PLAN OF THIS SUITE OR LIFE SAFETY PLAN
 FOR THE FULL SUITE. 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS, COMMERCIAL:
 (6) LIFE SAFETY
 (7) MEANS OF EGRESS & SPECIFIC OCCUPANCY REQUIREMENTS
 PLEASE INCLUDE THE COMMON CORRIDORS OR HALLWAYS,
 1028.1.2 EXTERIOR CORRIDORS, THE MINIMUM CLEAR WIDTH OF
 SUCH CORRIDORS SHALL BE SUFFICIENT TO ACCOMMODATE THE
 OCCUPANT LOAD BUT SHALL IN NO CASE BE LESS THAN 6 FEET.
 THE CORRIDOR TO TTHE LEFT OF THE CLSSROOMS IS TO BE
 CONSIDERED AN EXTERIOR CORRIDOR. THE CORRIDOR DIRECTLY
 IN FRONT OF THE MAIN ENTRY AND CLASSROOM # 3 CAN'T BE
 DERTERMINED AT THIS TIME.
  
 THE SECOND ISSUE WITH THE CORRIDORS THAT SERVE THE
 EDUCATIONAL OCCUPANCY IS THE FIRE RATING OF THE
 CORRIDOR. TABLE 1017.1 REQUIRES THE CORRIDOR TO BE A 1
 HOUR RATING FOR BUILDINGS THAT ARE NOT FIRE
 SPRINKLERED, AND A EDUCATIONAL OCCUPANCY GREATER THAN
 30. PLANS INDICATE ONLY THE EDUCATIONAL OR CLASS ROOM
 ARE TO BE FIRE SPRINKLERED FROM THE NOTE# 3 OF SHEET
 A-1.0. AGAIN PLEASE PROVIDE CORRIDOR RATING S OUTSIDE
 OF THE TENANT UNIT.
  
 2) SHEET A-0.0 INDICATES THAT THE BUILDING TYPE TO BE A
 III-A, SPRINKLED:
 2A) IS THE TOTAL BUILDING SPRINKLERED?
 2B) THIS BUILDING TYPE IS INDICATED AS A TYPE IIIA IS
 THE BAR JOIST 1 HR PROTECTED? IT APPEARS THIS BUILDING
 COULD BE CLASSIFIED AS A III-B WITH AREA MODIFICATIONS
 506.1 & 506.2.
  
 3) SHEET A-1.0 INDICATES TWO DOORS IN SERIES LEADING
 FROM THE RECEPTION ROOM TO THE LUNCH ROOM, PLEASE
 REVIEW SECTION 11-4.13.7 AND FIGURE 26, TWO DOORS IN
 SERIES.
  
 4) SHEET A-1.0 THE SAME TWO DOORS ON THE LATCH SIDE
 WILL REQUIRE 18" CLEAR FOR MANEUVERING CLEARENCES.
 11-4.13.6.
  
 5) THE B. O. DOUG WISE WILL DETERMINE IF THE EXISTING
 SHOWER WILL REQUIRE ACCESSIBILITY, SINCE THIS IS TO BE
 USED AS A TEACHING TOOL. 11-4.21. SHOWER STALL
 REQUIREMENTS.
 MR. WISE HAS BEEN IN CONTACT WITH MR. TYLKA ALREADY FOR
 THIS PROJECT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.