2009-05-29 14:23:39REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. GREASE EXHAUST DUCTS SHALL BE FLANGED, GASKETED AND
 BOLTED TO THE INLET AND OUTLET OF THE FAN FOR IN-LINE
 FANS IN ACCORDANCE WITH FBC-M 506.3.2.3.
  
 2. DUCTS EXPOSED TO THE OUTSIDE ATMOSPHERE OR SUBJECT
 TO A CORROSIVE ENVIRONMENT SHALL BE PROTECTED AGAINST
 CORROSION IN AN APPROVED MANNER IN ACCORDANCE WITH
 FBC-M 506.2.
  
 3. A GREASE DUCT TEST IS REQUIRED FOR ALL JOINTS AND
 SEAMS IN THE PRESENCE OF THE CODE OFFICIAL IN
 ACCORDANCE WITH FBC-M 506.3.2.5. THE PROPOSED LOCATION
 OF THE DUCT WILL REQUIRE INSPECTION OF THE EXTERIOR
 DUCT PRIOR TO INSTALLATION. COORDINATE WITH FIELD
 INSPECTOR.
  
 4. PROVIDE STRUCTURAL CALCULATIONS FOR BUILDING PLAN
 REVIEW SHOWING THE EXISTING FLOOR/CEILING ASSEMBLY IS
 CAPABLE OF SUPPORTING ADDITIONAL LOADS ASSOCIATED WITH
 THE PROPOSED HOOD, DUCTWORK, WRAP AND PERSONNEL WORKING
 ON THE HOOD IN ACCORDANCE WITH FBC-M 506.3.3 AND 507.6.
  
 5. PROVIDE MANUFACTURERS OR OTHER SUPPORTING DATA
 SHOWING SUPPLY AND EXHAUST FANS ARE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. SEPARATE
 BUILDING PLAN REVIEW ALSO REQUIRED FOR THE WIND
 RESISTANCE CAPABILITIES OF FAN AND DUCT SUPPORTS.
  
 6. SUPPLY FAN APPEARS TO BE FACING THE REAR PARKING LOT
 OF THE BUILDING. MAKEUP AIR INTAKE OPENING LOCATIONS
 SHALL COMPLY WITH FBC-M SECTIONS 401.4 AND 401.4.1
  
 NOTE: SEPARATE PERMIT FOR FIRE SUPPRESSION SYSTEM
 REQUIRED PER FBC-M 509.1.
  