2009-06-15 09:47:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DECLARE WIND DESIGN CRITERIA, FBC1603.
  
 2. PROVIDE ATTACHMENT DETAILS TO SHOW HOW EXTERIOR
 EQUIPMENT AND DUCTS WILL RESIST WIND LOADS FBC1609.
  
 3. PROVIDE CALCULATIONS TO SHOW THAT THE EXISTING
 FLOOR/CEILING CAN SUPPORT THE LOADS CREATED BY THE NEW
 EQUIPMENT/DUCTS IN ADDITION TO OTHER DEAD AND LIVE
 LOADS. WHAT OCCUPANCY IS ON THE SECOND FLOOR (FBC
 CHAPTER 3)?
  
 4. PLEASE CLARIFY EXISTING CONDITONS. HOOD HANGING
 DETAIL (SHEET 3) SHOWS TRUSSES; SECTIONS SHOW "2X10
 WOOD STUDS;" DO YOU MEAN JOISTS? "STUDS" ARE INSTALLED
 VERTICALLY (COMPONENT OF A FRAME WALL). IT IS NOT CLEAR
 IF FLOOR JOISTS OR FLOOR TRUSSES ARE EXISTING.
  