Plan Review Notes
Plan Review Notes For Permit 09050271
Permit Number 09050271
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-15 13:23:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PRODUCT APPROVAL SUBMITTED IS EXPIRED, 2004 CODE
 RATHER THAN 2007. FAC9B-72.
  
 2. 3350PSI CONCRETE REQUIRED. FLOOR MOUNT WAS
 SPECIFIED; HOW HAVE YOU DETERMINED THAT THE CONCRETE
 HAS MET THIS REQUIREMENT, WHEN PATIO SLABS ARE
 TYPICALLY 2500PSI? EITHER PROVIDE EVIDENCE THAT THE
 CONCRETE MEETS MINIMUM STRENGTH REQUIREMENT OR USE
 CONCRETE BLOCK ANCHOR SPACING CHART.
  
 3. IT APPEARS THAT THIS PARCEL IS LOCATED IN EXPOSURE
 C. PLEASE SEE FBC R301, FBC1609, ASCE7-05.
  
  