| Plan Review Notes For Permit 09050247 |
| Permit Number |
09050247 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-28 13:48:14 | *****DENIED***** | | | | | | 1. THE PROJECT DETAIL AS DESCRIBED ON THE APPLICATION | | | IS FOR THE RECONFIGURATION OF SUITES 125 AND 150, | | | HOWEVER THE PLANS REFLECT THAT THE PROJECT SCOPE OF | | | WORK IS FOR SUITES 101 AND 103. PLEASE | | | CORRELATE/CLARIFY. | | | | | | 2. THE ACTUAL SUITE(S) SHALL BE INCLUDED IN THE ADDRESS | | | LISTED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 3. ON SHEET T, REFERENCE STANDARDS SHALL BE AS FOLLOWS: | | | FLORIDA FIRE PREVENTION CODE 2007 EDITION, NFPA 101 - | | | LIFE SAFETY CODE - 2006 EDITION, AND NFPA 1 - UNIFORM | | | FIRE CODE - 2006 EDITION. | | | | | | 4. ON SHEET E-2, ELECTRICAL NOTE #2, AMEND EDITION OF | | | NFPA 101 FROM 2003 TO 2006. | | | | | | 5. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|