| 2009-05-26 10:03:09 | **DENIED ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | AT A MINIMUM. |
| | 2007 FBC W/ 2009 REVISIONS. |
| | 2006 NFPA-101 |
| | |
| | |
| | 2) NOTE: PLEASE LABEL ALL MAINS. ONLY ONE IS INDICATED. |
| | WILL THERE NOW BE A TOTAL OF 6 MAINS? THIS IS WHAT THE |
| | RISER APPEARS TO SHOW. PLEASE LABEL, 1 OF X, 2 OF X, 3 |
| | OF X ETC. THE 1200 AMP MAIN IS SHOWN 1 OF 4, YET THIS |
| | APPEARS TO BE THE MAIN TO FEED GUTTER. THE TENANTS |
| | WOULD BE THEN TENANT MAINS? |
| | 230.2E |
| | |
| | 3) NOTE: PLEASE INDICATE CONDUCTORS FROM GUTTER TO |
| | METER AND METER TO NEW TENANT MAIN. PLEASE ALSO |
| | INDICATE A FLOATING NEUTRAL KIT IS REQUIRED IF THE 1200 |
| | AMP MAIN INDEED FEEDS GUTTER. |
| | 250.6,250.24,310.16,240.4. |
| | |
| | 4) NOTE: PLEASE INCLUDE THE LOAD ON THE EXISTING MAIN |
| | WITH THE ADDITION OF THE NEW LOAD FOR TENANT. |
| | 220. PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT |
| | 125%. |
| | |
| | 5) NOTE: PLEASE SEE CURRENT ADOPTED FLORIDA BUILDING |
| | CODE CHAPTER 13. A NOTE ON PLANS, MENTIONS THE SCONCES |
| | ARE NOT INCLUDED PER SECTION CITED. HOWEVER EVEN UNDER |
| | THE PREVIOUS CODES, THE SCONCES OR DECRETIVE TYPES OF |
| | FIXTURES WERE NEVER *EXEMPT*. THERE WAS AN ADDITIONAL |
| | ALLOWANCE FOR THOSE TYPES OF FIXTURE HOWEVER NOT |
| | EXEMPTED. IN BOTH CASES PLEASE SEE THE NEW ENERGY CODE |
| | AS THERE IS NO MORE ADDITIONAL ALLOWANCES FOR ANY |
| | DECRETIVE FIXTURES. ALL MUST BE FIGURED PER |
| | 13-415.AB.5. |
| | TRADE OFF OF SPACES IS NOT LONGER PERMITTED EITHER. |
| | PLEASE BE SURE TO SEE THE ADOPTED REVISIONS TO CHAPTER |
| | 13. |
| | |
| | 6) NOTE: THE UNIT/SUITE NEEDS TO BE DETERMINED AS |
| | CORRECT. PERMIT APPLICATION STATES 125 AND 150, YET |
| | PLANS CALL FOR SUITE #103. PLEASE CORRELATE ALL OF |
| | THESE AND ADJUST AS NEEDED. |
| | WHEN RE-SUBMITTING PLANS IT IS IMPORTANT TO INDICATE |
| | THE CORRECTED SUITE NUMBER TO FRONT COUNTER STAFF IN |
| | ORDER FOR SYSTEM TO BE UPDATED WITH CORRECTED |
| | INFORMATION. |
| | FAC 61G15-23.002, 61G1-16.004, FBC 106.5 |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |