| Plan Review Notes For Permit 09050240 |
| Permit Number |
09050240 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-26 12:12:46 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. THIS REVISION CONSTITUTES AN EXPANSION OF THE SCOPE | | | OF WORK PROPOSED ON THE PERMIT APPLICATION AND ORIGINAL | | | PLANS. SCOPE ON PERMIT APPLICATION SHALL BE EXPANDED | | | AND SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR | | | MECHANICAL. VALUE SHALL BE BASED ON ACTUAL MECHANICAL | | | SCOPE. | | | | | | 2. THIS APPEARS TO BE AN ADDITION OF AIR CONDITIONING | | | TO A PREVIOUSLY UNCONDITIONED BUILDING. THIS BUILDING | | | MUST BE BROUGHT INTO FULL COMPLIANCE WITH THE FLORIDA | | | ENERGY EFFICIENCY CODE IN ACCORDANCE WITH FBC-B | | | 13-101.4.1.2. PROVIDE FULL ENERGY CODE COMPLIANCE FORMS | | | AND COOLING/HEATING LOAD CALCULATIONS TO DEMONSTRATE | | | COMPLIANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|