2009-05-26 18:45:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THIS IS A RENTAL PROPERTY; THEREFORE, AN
 OWNER/BUILDER PERMIT CANNOT BE ISSUED, FS489. PLEASE
 HAVE A CONTRACTOR LICENSED TO PERFORM THIS WORK APPLY
 FOR PERMIT.
  
 2. A BUILDING PERMIT IS REUQIRED FOR THE STRUCTURAL
 WORK, FS489.
  
 3. PROVIDE A SITE PLAN SHOWING STRUCTURE LOCATION AND
 DISTANCE TO PROPERTY LINE, FBC R301.
  
 4. PROVIDE A STRUCTURAL DETAIL (WALL SECTION) OF THE
 PROPOSED IMPROVEMENT. TRUSS ENGINEERING WAS PROVIDED
 BUT A WALL SECTION IS REQUIRED SHOWING ALL ELEMENTS
 SUCH AS FASCIA, INSULATION, DRYWALL, ETC.
  
 5. PROVIDE A REASONABLE VALUE FOR THIS JOB. PAY
 ADDITIONAL FEES ON VALUE PRIOR TO RESUBMITTAL. IF A
 REASONABLE VALUE IS NOT PROVIDED AND FEES PAID, THIS
 WILL DELAY THE PERMIT PROCESS AS REVIEWS CANNOT BE
 PERFORMED UNTIL APPROPRIATE FEES ARE PAID.
  
 6. PROVIDE THE FOLLOWING INFORMATION FOR THE ROOF:
  
 PRODUCT APPROVAL - SELECT APPROVED ASSEMBLY AND
 INDICATE PROPOSED FASTENER
 ENHANCED FASTENING, IF REQUIRED (ENGINEERING MAY BE
 REQUIRED)
  
  
  
  
  
  