| 2009-05-18 13:28:56 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE |
| | DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES. |
| | 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE |
| | DETECTORS. |
| | SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO |
| | NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY |
| | THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED |
| | SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM, |
| | PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS. |
| | |
| | |
| | 2) NOTE: THE RECEPTACLE SPACING ALONG KITCHEN COUNTER |
| | SPACE DOES NOT MEET 210.52C1. WITHIN 2FT OF THE END OF |
| | A COUNTER EDGE, AND 4FT THERE AFTER. SEE WALL/COUNTER |
| | SPACE IN WHICH THIS DOE NOT MEET SECTION GIVEN. |
| | |
| | 3) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES IN |
| | KITCHEN SHALL BE GFI/GFI PROTECTED. PLEASE SHOW. |
| | |
| | 4) NOTE: PLEASE SEE 210.52F FOR MISSING WASHER/LAUNDRY |
| | CIRCUIT. PLEASE ALSO SEE 220.52 FOR REQUIRED VA TO BE |
| | FIGURED. |
| | |
| | 5) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS. THE |
| | SUBMITTED CALCULATIONS DO NOT DEPICT ANY LOAD |
| | CALCULATIONS OUT OF THE NEC. |
| | PLEASE ALSO SEE 4220.13 FOR WATER HEATERS AS LOADS ARE |
| | FIGURED AT 125%. |
| | |
| | 5) NOTE: THE RISER INDICATES THE UNDERGROUND TO A |
| | HAND-HOLE. BEING THE CASE THIS WOULD REQUIRE THE |
| | CONDUCTORS TO FALL UNDER THE NEC AND 310.16, 310.15B6. |
| | PLEASE INCLUDE CONDUCTORS. |
| | |
| | 6) NOTE: PLEASE INCLUDE AIC RATING FOR NEW SERVICE |
| | EQUIPMENT. 110.9 |
| | |
| | 7) NOTE: PLEASE SEE 210.52E AND 210.8A3 FOR THE |
| | REQUIRED MISSING FRONT AND REAR GFI RECEPTACLES. |
| | |
| | 8) NOTE: PLEASE SEE FS 481.229 AND 471.003 WHEN MEETING |
| | THE EXCEPTIONS IN THE STATUTES FOR DESIGN PROFESSIONAL, |
| | THE DESIGNER OF RECORD SHALL PRINT AND SIGN NAME TAKING |
| | RESPONSIBILITY OF SAID PLANS. |
| | |
| | 9) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL |
| | LOCATIONS IN WHICH THE RECEPTACLE SPACE FOR WALL AREAS |
| | NEEDS TO BE ADJUSTED. |
| | |
| | 10) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER/DISPOSAL |
| | WHEN BEING FED TO THE SAME YOKE SHALL BE ON A 2-POLE |
| | BREAKER. |
| | |
| | 11) NOTE: PLEASE SHOW LOCATION OF MISSING DISCONNECT |
| | FOR THE AHU. 440.12 AND 440.14 |
| | |
| | 12) NOTE: PLEASE SEE 210.63 FOR MISSING ATTIC SPACE |
| | LIGHT REQUIRED. |
| | |
| | 13) NOTE: PLEASE LIST ANY RECESSED TYPE LIGHT FIXTURES |
| | TO MEET FBC 13-606.AB.1.2.3.4 |
| | |
| | 14) NOTE: PLEASE SUBMIT TWO COPIES OF PLANS. FBC 106.1, |
| | 106.1.1 |
| | |
| | 15) NOTE: PLEASE COORDINATE ELECTRICAL WITH MECHANICAL |
| | PLANS. ONE SHOWS 10KW AND THE OTHER 8KW. PLEASE KNOW |
| | THAT THIS WILL AFFECT THE OVER CURRENT PROTECTION IF |
| | THIS IS 8KW AS THE OCP ON PANEL IS SHOWN AS 60AMP WHICH |
| | MAY BE TOO HIGH. SEE 424.3B. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |