2009-05-18 13:28:56**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE
 DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES.
 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE
 DETECTORS.
 SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO
 NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY
 THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED
 SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS.
  
  
 2) NOTE: THE RECEPTACLE SPACING ALONG KITCHEN COUNTER
 SPACE DOES NOT MEET 210.52C1. WITHIN 2FT OF THE END OF
 A COUNTER EDGE, AND 4FT THERE AFTER. SEE WALL/COUNTER
 SPACE IN WHICH THIS DOE NOT MEET SECTION GIVEN.
  
 3) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES IN
 KITCHEN SHALL BE GFI/GFI PROTECTED. PLEASE SHOW.
  
 4) NOTE: PLEASE SEE 210.52F FOR MISSING WASHER/LAUNDRY
 CIRCUIT. PLEASE ALSO SEE 220.52 FOR REQUIRED VA TO BE
 FIGURED.
  
 5) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS. THE
 SUBMITTED CALCULATIONS DO NOT DEPICT ANY LOAD
 CALCULATIONS OUT OF THE NEC.
 PLEASE ALSO SEE 4220.13 FOR WATER HEATERS AS LOADS ARE
 FIGURED AT 125%.
  
 5) NOTE: THE RISER INDICATES THE UNDERGROUND TO A
 HAND-HOLE. BEING THE CASE THIS WOULD REQUIRE THE
 CONDUCTORS TO FALL UNDER THE NEC AND 310.16, 310.15B6.
 PLEASE INCLUDE CONDUCTORS.
  
 6) NOTE: PLEASE INCLUDE AIC RATING FOR NEW SERVICE
 EQUIPMENT. 110.9
  
 7) NOTE: PLEASE SEE 210.52E AND 210.8A3 FOR THE
 REQUIRED MISSING FRONT AND REAR GFI RECEPTACLES.
  
 8) NOTE: PLEASE SEE FS 481.229 AND 471.003 WHEN MEETING
 THE EXCEPTIONS IN THE STATUTES FOR DESIGN PROFESSIONAL,
 THE DESIGNER OF RECORD SHALL PRINT AND SIGN NAME TAKING
 RESPONSIBILITY OF SAID PLANS.
  
 9) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL
 LOCATIONS IN WHICH THE RECEPTACLE SPACE FOR WALL AREAS
 NEEDS TO BE ADJUSTED.
  
 10) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER/DISPOSAL
 WHEN BEING FED TO THE SAME YOKE SHALL BE ON A 2-POLE
 BREAKER.
  
 11) NOTE: PLEASE SHOW LOCATION OF MISSING DISCONNECT
 FOR THE AHU. 440.12 AND 440.14
  
 12) NOTE: PLEASE SEE 210.63 FOR MISSING ATTIC SPACE
 LIGHT REQUIRED.
  
 13) NOTE: PLEASE LIST ANY RECESSED TYPE LIGHT FIXTURES
 TO MEET FBC 13-606.AB.1.2.3.4
  
 14) NOTE: PLEASE SUBMIT TWO COPIES OF PLANS. FBC 106.1,
 106.1.1
  
 15) NOTE: PLEASE COORDINATE ELECTRICAL WITH MECHANICAL
 PLANS. ONE SHOWS 10KW AND THE OTHER 8KW. PLEASE KNOW
 THAT THIS WILL AFFECT THE OVER CURRENT PROTECTION IF
 THIS IS 8KW AS THE OCP ON PANEL IS SHOWN AS 60AMP WHICH
 MAY BE TOO HIGH. SEE 424.3B.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO