| Plan Review Notes For Permit 09050228 |
| Permit Number |
09050228 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-05-14 13:04:03 | RESIDENTIAL (R3) RE-ROOFING, BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS. | | | SELECTED FLAT ROOF ASSEMBLY ON NOA 08-0226.06 CALLS FOR | | | THREE ROWS OF NAILS IN THE CENTER OF SHEET FOR ROOF | | | ZONE 1. ENGINEER SPECIFIES TWO ROWS OF NAILS FOR ROOF | | | ZONE 1. ENGINEER CAN'T REDUCE THE NUMBER OF NAILS. | | | REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | (561)805-6712 |
|