| 2009-07-22 18:19:20 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 FUEL GAS |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 |
| | FUEL GAS CODE. - THE DRAWING IS NOT IN ISOMETRIC FORM |
| | AND DOES NOT SHOW THE LENGTHS OF EACH CUT SECTION. THE |
| | DRAWING DOES NOT REFLECT THE PIPING SHOWN ON THE FLAT |
| | DRAWING. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. NOT ALL LENGHTS |
| | SHOWN. -- SEE EXAMPLE OF RISER DIAGRAM IN ISOMETRIC |
| | FORM. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. - PIPING |
| | MATERIAL IS NOT INDICATED ON THE RISER DIAGRAM AND NOT |
| | ALL PIPING IS INDICATED ON THE FLAT DRAWING. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1/G2412.8 THRU G2413.6.1. AND TABLES |
| | 402.4(1) THRU |
| | 402.4(35)/G2413.4(1) THRU G2413.4(8). - THE BTU LOAD |
| | FOR THE FUTURE GENERATOR IS NOT SHOWN OR ADDED TO THE |
| | TOTAL BTU LOAD. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED.-- THE MANUF. |
| | SHEET FOR THE RANGE INDICATES THE LOAD AT 140,000 |
| | BTU'S, (6 BURNERS @ 18,000 EACH, 1 GRIDDLE @ 18,000 & 1 |
| | GRILL @ 14,000), BUT THE PLANS INDICATE ONLY 100,000 |
| | BTU'S . THERE IS NO BTU LOAD INDICATED FOR THE |
| | GENERATOR. PLEASE CORRELATE. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN |
| | COMMENT 1 IS ADDRESSED. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2007 FUEL |
| | GAS CODE SECTION 304 & G2407. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 & G2413.2. |
| | ****RESPONSE NOTED, ALL FUTURE APPLIANCES SHALL BE |
| | INDICATED AS SUCH ON THE ISOMETRIC. A SEPARATE PERMIT |
| | WILL BE REQUIRED WHEN THE APPLIANCES ARE INSTALLED. |
| | |
| | B. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |