| 2009-05-13 08:43:38 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 FUEL GAS |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 |
| | FUEL GAS CODE. - THE DRAWING IS NOT IN ISOMETRIC FORM |
| | AND DOES NOT SHOW THE LENGTHS OF EACH CUT SECTION. THE |
| | DRAWING DOES NOT REFLECT THE PIPING SHOWN ON THE FLAT |
| | DRAWING. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. - PIPING |
| | MATERIAL IS NOT INDICATED ON THE RISER DIAGRAM AND NOT |
| | ALL PIPING IS INDICATED ON THE FLAT DRAWING. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1/G2412.8 THRU G2413.6.1. AND TABLES |
| | 402.4(1) THRU |
| | 402.4(35)/G2413.4(1) THRU G2413.4(8). - THE BTU LOAD |
| | FOR THE FUTURE GENERATOR IS NOT SHOWN OR ADDED TO THE |
| | TOTAL BTU LOAD. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN |
| | COMMENT 1 IS ADDRESSED. |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2007 FUEL |
| | GAS CODE SECTION 304 & G2407. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 & G2413.2. |
| | |
| | B. 108.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION |
| | OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. - THE VALUATION OF $2,200.00 FOR ALL THE |
| | APPLIANCES, THE PIPING & LABOR APPEARS TO BE LOW. |
| | PLEASE INDICATE THE TOTAL COAST OF THE JOB. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |