| Plan Review Notes For Permit 09050218 |
| Permit Number |
09050218 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-13 15:46:33 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 | | | REVISIONS. | | | | | | 1- ACCORDION SHUTTERS DRAWINGS NO 05-578 SUBMITTED | | | DON'T CORRESPOND TO FLORIDA FL10753-R1 PRODUCT APPROVAL | | | SUBMITTED. GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD | | | CORRESPONDING DRAWINGS TO FLORIDA PRODUCT APPROVAL | | | SUBMITTED. | | | | | | 2- REVISE DESIGN PRESSURES CALCULATIONS SUBMITTED. | | | ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA | | | RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE | | | "C". SEE REVISED AND NEW SECTIONS R301.2.1.4 THRU | | | R301.2.1.4.3 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 3- PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED | | | SAMPLE. ALSO, CLEARLY MARK ON SHUTTERS DRAWINGS | | | SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILT | | | OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE | | | USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|