2009-06-11 12:23:082007 FBC
 INSTALL LP GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY LARGER ANCHORS WITH MORE EMBED DEPTH OR
 PROVIDE SIGNED AND SEALED CALCULATIONS FROM A FLORIDA
 LICENSED ENGINEER WHICH SHOW THAT THE FOUR 5/16" X
 1-3/4" ANCHORS ARE ADEQUATE TO RESIST 140 MPH WINDLOAD
 FORCES FOR OVERTURNING, SLIDING AND UPLIFT AS REQUIRED
 BY FBC 1604.9.
  
 2) AS THE GENERATOR IS LOCATED AT THE CARPORT, SPECIFY
 THE PROTECTION THAT WILL BE PROVIDED. SEE FBC M303.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]