| 2009-06-11 12:23:08 | 2007 FBC | | | INSTALL LP GENERATOR | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY LARGER ANCHORS WITH MORE EMBED DEPTH OR | | | PROVIDE SIGNED AND SEALED CALCULATIONS FROM A FLORIDA | | | LICENSED ENGINEER WHICH SHOW THAT THE FOUR 5/16" X | | | 1-3/4" ANCHORS ARE ADEQUATE TO RESIST 140 MPH WINDLOAD | | | FORCES FOR OVERTURNING, SLIDING AND UPLIFT AS REQUIRED | | | BY FBC 1604.9. | | | | | | 2) AS THE GENERATOR IS LOCATED AT THE CARPORT, SPECIFY | | | THE PROTECTION THAT WILL BE PROVIDED. SEE FBC M303.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|