| 2009-07-03 08:25:09 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLANS SUBMITTED DO NOT CONTAIN ANY DESIGN |
| | PROFESSIONAL SIGNED, DATED OR SEALED ON ELECTRICAL |
| | PLANS. PLEASE SEE 481.229, 471.003. PLANS ARE FOR A |
| | COMMERCIAL HIGH-RISE MUST MEET THESE SECTIONS. |
| | |
| | 2) NOTE: PLEASE SEE BEDRM #2 WHICH STILL HAS MISSING |
| | RECEPTACLE REQUIRED PER 210.52 FOR 2FT OR MORE OF WALL |
| | SPACE. |
| | |
| | 3) NOTE: PREVIOUS NOTES WITH RESPECT TO THE REQUIRED |
| | CIRCUITING AND SMALL APPLIANCE CIRCUITS FOR KITCHEN, |
| | DINING AND AREAS OF THE LIKE. THE PLANS NOW INDICATE |
| | ONLY ONE SMALL APPLIANCE CIRCUIT FOR THE ENTIRE |
| | KITCHEN. TWO ARE REQUIRED AT A MINIMUM. AT THE TIME |
| | THIS BUILDING WAS CONSTRUCTED THESE UNITS HAD TWO SMALL |
| | APPLIANCE CIRCUITS AT A MINIMUM NOW ONLY SHOWS ONE IN |
| | KITCHEN. |
| | 210.52B1, 210.11C1, 220.52 |
| | |
| | 4) NOTE: PANEL SCHEDULE STILL INDICATES TWO WATER |
| | HEATERS HOWEVER NONE ARE SHOWN ON PLANS. PLEASE KNOW |
| | THAT ALL CONTINUOUS LOADS SHALL BE BASED AT 125%. |
| | 422.13 |
| | WHEN SHOWING THESE ITEMS ON PLANS, PLEASE BE SURE TO |
| | INCLUDE THE NEW OR EXISTING DISCONNECTS PER 422.30,31 |
| | ETC |
| | |
| | 5) NOTE: NOTES ON PLANS MENTION TO WIRE SMOKE ALARMS TO |
| | EXISTING FIRE ALARM SYSTEM. PLEASE CHECK WITH THE FIRE |
| | MARSHAL AS UNIT SINGLE STATION DEVICES SHOULD NOT BE |
| | CONNECTED TO BASE BUILDING. IT MAY BE A TROUBLE SIGNAL |
| | OF SOME TYPE. PLEASE CHECK WITH FIRE PLAN REVIEW. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |