| Date |
Text |
| 2009-05-22 08:47:22 | **DENIED ** |
| | |
| | 1) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS PER |
| | MINIMUM CODE REQUIREMENTS. |
| | PLEASE SEE DINING, BREAKFAST AREAS AND AREA OF THE LIKE |
| | PER 210.52B1 ARE REQUIRED TO BE ON ONE OR MORE OF THE |
| | SMALL APPLIANCE CIRCUITS. THE CIRCUIT IN ONE OF THESE |
| | AREAS IS SHOWN AS CIRCUIT #17 WHICH IS A BEDROOM ARC |
| | FAULT CIRCUIT WHICH IS NOT PERMITTED. |
| | ANOTHER WOULD BE THE SMOKE ALARMS. PLEASE ALSO SEE |
| | 210.12 FOR REQUIRED ARC FAULT PROTECTION. |
| | PLEASE ALSO BE SURE TO SEE OTHER CIRCUITS ON PANEL |
| | SCHEDULE WHICH DO NOT GO TO ANYTHING. 408.4. |
| | |
| | 2) NOTE: PLANS APPEAR TO HAVE LIGHT LOCATIONS WHICH ARE |
| | SWITCHED FROM MORE THAN ONE LOCATION HOWEVER THE |
| | SWITCHES ARE NOT SHOWN AS 3-WAYS. PLEASE ADJUST. NEC |
| | 300. |
| | FBC 106.1.1 |
| | |
| | 3) NOTE: PLEASE SEE 422.13 FOR STORAGE TYPE WATER |
| | HEATERS WHICH REQUIRES LOAD TO BE FIGURED AT 125%. |
| | |
| | 4) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| | CODES AT A MINIMUM. |
| | 2002 NFPA-72 |
| | 2007 FBC W/ 2009 REVISIONS |
| | |
| | 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING. |
| | THERE ARE SEVERAL LOCATIONS IN WHICH RECEPTACLES ARE |
| | REQUIRED. SOME NEED TO BE ADDED AND SOME NEED TO BE |
| | RELOCATED IN ORDER TO BE CODE COMPLIANT. |
| | |
| | 6) NOTE: PLEASE SEE 210.11C1, AND 220.52 FOR REQUIRED |
| | LOAD TO BE FIGURED FOR THE ONE OR MORE SMALL APPLIANCE |
| | CIRCUITS. THIS IS RELEVANT TO THE COMMENT NUMBER ONE |
| | ABOVE. WHEN YOU HAVE MORE THAN TWO SMALL APPLIANCE |
| | CIRCUITS FOR DINING ROOMS, AREAS LIKE BREAKFAST AREAS |
| | AND THE LIKE, EACH ONE REQUIRES 1500 VA FOR EACH. |
| | |
| | 7) NOTE: PLEASE SEE 210.11C3 FOR RECEPTACLE MISSING |
| | ALONG KITCHEN COUNTER SPACE. PLEASE ALSO SEE 210.8A6 |
| | FOR REQUIRED GFCI PROTECTION. |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |