Plan Review Notes
Plan Review Notes For Permit 09050177
Permit Number 09050177
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-18 11:01:22**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE
 DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES.
 PLEASE PROVIDE A LAYOUT OF THE EXISTING DWELLING
 SHOWING ALL NEW OR EXISTING SMOKE ALARM DEVICE
 LOCATIONS MEETINGS CURRENT CODES. PLEASE SEE NFPA-72
 FOR LOCATIONS WHICH REQUIRE THESE TO BE HARD WIRED.
 11.5.1. PLEASE ALSO SEE 11.8.3 AS ALL DEVICES SHALL BE
 20FT FROM COOKING APPLIANCES UNLESS MEETING EXCEPTIONS
 TO A SPECIFIC TYPE OF DEVICE.
 PLEASE ALSO SEE FS 553.885 FOR REQUIRED CARBON MONOXIDE
 DETECTORS. AS THE DWELLING/PLANS DO NOT INDICATE AN
 ATTACHED GARAGE OF GAS APPLIANCE IT IS NOT KNOWN AT
 THIS TIME.
  
 2) NOTE: THE RECEPTACLE SPACING ALONG KITCHEN COUNTER
 SPACE DOES NOT MEET 210.52C1.
 THIS COULD HAVE BEEN REDLINED HOWEVER COMMENT #1 NEEDS
 TO BE ADDRESSED.
  
 3) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES IN
 KITCHEN SHALL BE GFI/GFI PROTECTED. PLEASE SHOW.
 PLEASE ALSO CLARIFY THE RECEPTACLE NOW SHOWN IN THE
 MIDDLE OF THE FLOOR IN KITCHEN. THIS APPEARS IT MAY BE
 NEW INSTALLED.
  
 4) NOTE: BASED ON THE SCOPE OF WORK AND THE POSSIBLE
 NEW WORK BEING NEEDED TO MEET THE MINIMUM CODES, THE
 VALUE FOR THE SCOPE OF WORK IS LOW AND NEEDS TO BE
 ADJUSTED.
 FBC 108.3
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  