| 2009-05-18 11:01:22 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE |
| | DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES. |
| | PLEASE PROVIDE A LAYOUT OF THE EXISTING DWELLING |
| | SHOWING ALL NEW OR EXISTING SMOKE ALARM DEVICE |
| | LOCATIONS MEETINGS CURRENT CODES. PLEASE SEE NFPA-72 |
| | FOR LOCATIONS WHICH REQUIRE THESE TO BE HARD WIRED. |
| | 11.5.1. PLEASE ALSO SEE 11.8.3 AS ALL DEVICES SHALL BE |
| | 20FT FROM COOKING APPLIANCES UNLESS MEETING EXCEPTIONS |
| | TO A SPECIFIC TYPE OF DEVICE. |
| | PLEASE ALSO SEE FS 553.885 FOR REQUIRED CARBON MONOXIDE |
| | DETECTORS. AS THE DWELLING/PLANS DO NOT INDICATE AN |
| | ATTACHED GARAGE OF GAS APPLIANCE IT IS NOT KNOWN AT |
| | THIS TIME. |
| | |
| | 2) NOTE: THE RECEPTACLE SPACING ALONG KITCHEN COUNTER |
| | SPACE DOES NOT MEET 210.52C1. |
| | THIS COULD HAVE BEEN REDLINED HOWEVER COMMENT #1 NEEDS |
| | TO BE ADDRESSED. |
| | |
| | 3) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES IN |
| | KITCHEN SHALL BE GFI/GFI PROTECTED. PLEASE SHOW. |
| | PLEASE ALSO CLARIFY THE RECEPTACLE NOW SHOWN IN THE |
| | MIDDLE OF THE FLOOR IN KITCHEN. THIS APPEARS IT MAY BE |
| | NEW INSTALLED. |
| | |
| | 4) NOTE: BASED ON THE SCOPE OF WORK AND THE POSSIBLE |
| | NEW WORK BEING NEEDED TO MEET THE MINIMUM CODES, THE |
| | VALUE FOR THE SCOPE OF WORK IS LOW AND NEEDS TO BE |
| | ADJUSTED. |
| | FBC 108.3 |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |