| Notes |
| Date |
Text |
| 2009-05-18 16:32:27 | **DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE LIST THE FOLLOWING CODES: AS OF | | | DECEMBER 31ST 2008, FAC 69A-60.004 ADOPTED THE 2006 | | | NFPA-101. THE ELECTRICAL PLANS STATE THE 2003 EDITION. | | | PER THE ELECTRICAL PLANS, THE EDITION OF NFPA-70 STATES | | | THE 2008 EDITION. THE STATE OF FLORIDA ADOPTED THE 2005 | | | EDITION OF NFPA-70 ON DECEMBER 8TH, 2006. UNDER THE | | | 2007 FBC WITH THE 2009 REVISIONS CHAPTER 35 STILL | | | REFLECTS THE 2005. THE STATE HAS NOT ADOPTED THE 2008 | | | NEC. ( IT HAS NO BEEN TABLED TO AN UNKNOWN DATE) | | | | | | 2) NOTE: PLEASE SEE CONFERENCE ROOM IN SECOND TENANT | | | SPACE MEETING FBC 13-415.AB.1.1, .1.2 FOR CONTROLS. | | | | | | 3) NOTE: PLEASE LIST THE REQUIRED NOTES FOR FBC | | | 13-413.AB.2 | | | ** THE NOTES AS LISTED DIRECTLY IN THE CODE BOOK IS THE | | | INTENT TO HAVE ON PLANS. | | | | | | 4) NOTE: PLEASE SEE THE 2009 REVISIONS TO THE 2007 FBC | | | AS THE CODE SECTIONS AND LIGHTING PERFORMANCE | | | CALCULATIONS HAVE BEEN UPDATED. | | | THE SECTIONS ON PLANS ARE FROM THE PREVIOUS | | | CODES/REVISIONS. | | | KEEP IN MIND THE NEW SPACE BY SPACE DOES NOT ALLOW | | | TRADE OFFS IN OTHER AREAS. 13-415.AB.5. | | | | | | | | | | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|