Plan Review Notes
Plan Review Notes For Permit 09050149
Permit Number 09050149
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-18 16:32:27**DENIED REVIEW **
  
 1) NOTE: PLEASE LIST THE FOLLOWING CODES: AS OF
 DECEMBER 31ST 2008, FAC 69A-60.004 ADOPTED THE 2006
 NFPA-101. THE ELECTRICAL PLANS STATE THE 2003 EDITION.
 PER THE ELECTRICAL PLANS, THE EDITION OF NFPA-70 STATES
 THE 2008 EDITION. THE STATE OF FLORIDA ADOPTED THE 2005
 EDITION OF NFPA-70 ON DECEMBER 8TH, 2006. UNDER THE
 2007 FBC WITH THE 2009 REVISIONS CHAPTER 35 STILL
 REFLECTS THE 2005. THE STATE HAS NOT ADOPTED THE 2008
 NEC. ( IT HAS NO BEEN TABLED TO AN UNKNOWN DATE)
  
 2) NOTE: PLEASE SEE CONFERENCE ROOM IN SECOND TENANT
 SPACE MEETING FBC 13-415.AB.1.1, .1.2 FOR CONTROLS.
  
 3) NOTE: PLEASE LIST THE REQUIRED NOTES FOR FBC
 13-413.AB.2
 ** THE NOTES AS LISTED DIRECTLY IN THE CODE BOOK IS THE
 INTENT TO HAVE ON PLANS.
  
 4) NOTE: PLEASE SEE THE 2009 REVISIONS TO THE 2007 FBC
 AS THE CODE SECTIONS AND LIGHTING PERFORMANCE
 CALCULATIONS HAVE BEEN UPDATED.
 THE SECTIONS ON PLANS ARE FROM THE PREVIOUS
 CODES/REVISIONS.
 KEEP IN MIND THE NEW SPACE BY SPACE DOES NOT ALLOW
 TRADE OFFS IN OTHER AREAS. 13-415.AB.5.
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  