| Plan Review Notes For Permit 09050121 |
| Permit Number |
09050121 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-11-06 11:18:31 | PROVISO: | | | | | | PROVIDE A MINIMUM OF 400 CFM OUTSIDE AIR FOR THE | | | PROPOSED NEW USE OF THIS SPACE IN ACCORDANCE WITH | | | FBC-EB 901.2 AND 909.1. A TEST AND BALANCE REPORT SHALL | | | BE PROVIDED TO VERIFY VENTILATION RATES PRIOR TO FINAL | | | INSPACTION IN ACCORDANCE WITH FBC-M 403.3.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|