| 2009-05-15 13:11:33 | BUILDING PLAN REVIEW |
| | PERMIT: 09050121 |
| | ADD: 5115 S DIXIE HWY |
| | CONT: PRO-BUILT |
| | TEL: (561)444-3008 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS, 2007 EXISTING BUILDING |
| | CODE W/ 2009 SUPPLEMENTS, PLEASE UPDATE APPLICABLE |
| | CODES. |
| | |
| | 2) CODE ANALYSIS INDICATES THIS TO BE A TYPE IV |
| | BUILDING WHICH IS HEAVY TIMBER, PLEASE CORRECT, TABLE |
| | 503. |
| | |
| | 3) SHEET A-1 DOOR# 1 DOES NOT INDICATE THIS IS A NEW |
| | CUT IN OPENING, PLEASE SEE INTERIOR DEMO PERMIT |
| | 09040632 AND NOTE # 5 WHICH DEALS WITH THE NEW DOORWAY |
| | BEING CUT INTO THE WALL AND BUILDING PROVISO: DEMO |
| | NOTE# 5 TO BE DETERMINED BY ZONING DEPARTMENT , BLDG IS |
| | OK WITH SET BACK REQUIREMENTS TABLE 602. THE NEW PLANS |
| | FAIL TO INDICATE HOW THE BLOCK WALL WILL BE FITTED WITH |
| | COLUMNS AND EITHER BEAM OR LINTEL. ALSO MISSING PRODUCT |
| | APPROVALS FOR THE NEW LINTEL & DOOR OPENING. |
| | |
| | 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 4A) LINTEL |
| | 4B) EXTERIOR DOOR |
| | |
| | 5) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6) THE SWING RESTROOM DOOR AND DOOR # 4 ARE MISSING THE |
| | REQUIRED 18" LATCH SIDE. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 7) WINDOW E IS A HAZARDOUS LOCATION: WILL REQUIRE |
| | SAFETY GLAZING. 2406.3(6). |
| | |
| | 8) THIS MAY BE A CHANGE OF OCCUPANCY : BEFORE A PERMIT |
| | TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID |
| | TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS |
| | MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |