| Plan Review Notes For Permit 09050096 |
| Permit Number |
09050096 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-11 14:17:16 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SHUTTER MOUNTING CONNECTION TYPE STATES BUILDOUT, | | | BUT INSIDE MOUNT IS ALSO INDICATED ON PRODUCT APPROVAL. | | | THE SPAN IS LESS THAN THE OPENING; THE SPAN FOR AN | | | INSIDE MOUNT IS SMALLER BUT SHOULD BE LARGER FOR A | | | BUILD OUT. ANCHOR SPACING IS DETERMINED BY MOUNTING | | | TYPE AND DESIGN PRESSURE; PLEASE CLARIFY SO THAT CODE | | | COMPLIANCE CAN BE DETERMINED. IF TOP AND BOTTOM USE | | | DIFFERENT MOUNTING DETAILS, PLEASE SPECIFY BOTH. | | | | | | 2. CONCRETE IS SPECIFIED AS SUBSTRATE; IS THIS INTO A | | | PATIO SLAB? THE SLABS FOR HOUSES IN THIS DEVELOPMENT | | | WERE TYPICALLY 2500PSI, NOT 3000 PSI (MINIMUM STRENGTH | | | REQUIREMENT ON PRODUCT APPROVAL, SHEET 5). | | | | | | 3. A .71 FACTOR FOR 2" EDGE DISTANCE TO BE APPLIED TO | | | ANCHOR SPACING. PLEASE CONFIRM THAT THIS HAS BEEN | | | APPLIED. |
|