| 2009-09-30 16:38:41 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | MUNICIPAL CODE CITY WPB |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN |
| | DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3 |
| | DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO |
| | THE SANITARY DRAINAGE SYSTEM. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE RESPONSE THAT THE FLOOR |
| | DRAIN IS CONNECTED TO THE SANITARY SYSTEM IS NOT WHAT |
| | IS SHOWN ON THE PLANS. THE PLAN SHOW ALL THE AHU & A/C |
| | UNITS DRAINING INTO THE EXISTING 2 INCH CONDENSATE |
| | LINE. CONDENSATE SHALL NOT DRAIN INTO THE SANITARY PER |
| | THE WEST PALM BEACH CITY CODE ARTICLE III SECTION |
| | 90-125(5). PLEASE CLARIFY. IS THIS A CONDENSATE SYSTEM |
| | AS INDICATED OR A SANITARY SYSTEM IN WHICH CASE THE |
| | CONDENSATE SHALL NOT DRAIN INTO PER CITY CODE. |
| | |
| | 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC |
| | UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION |
| | 608. PLEASE INDICATE METHOD. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED. THE BACKFLOW SHALL BE INSTALLED A |
| | MAXIMUM 4 FEET ABOVE THE FLOOR FOR TESTING AND |
| | CERTIFICATION AND SHALL HAVE DRAIN LINE AND AN AIR GAP |
| | TO AN APPROVED INDIRECT WASTE RECEPTOR. MANUF |
| | INSTALLATION INSTRUCTIONS.SECTION 301.2. |
| | |
| | 3. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |