Plan Review Notes
Plan Review Notes For Permit 09050056
Permit Number 09050056
Review Stop P
Sequence Number 2
Notes
Date Text
2009-08-14 15:47:04DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 MUNICIPAL CODE CITY WPB
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN
 DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3
 DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO
 THE SANITARY DRAINAGE SYSTEM.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC
 UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION
 608. PLEASE INDICATE METHOD.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. PLANS SHALL BE DESIGNED PER THE CURRENT CODE CYCLE
 WHICH IS FBC-2007 W/2009 SUPPLEMENTS. PLEASE INDICATE
 ON PLANS. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  