| Date |
Text |
| 2009-08-14 15:47:04 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | MUNICIPAL CODE CITY WPB |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN |
| | DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3 |
| | DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO |
| | THE SANITARY DRAINAGE SYSTEM. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC |
| | UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION |
| | 608. PLEASE INDICATE METHOD. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 3. PLANS SHALL BE DESIGNED PER THE CURRENT CODE CYCLE |
| | WHICH IS FBC-2007 W/2009 SUPPLEMENTS. PLEASE INDICATE |
| | ON PLANS. SECTION 106.1.1. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |