| Plan Review Notes For Permit 09050056 |
| Permit Number |
09050056 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-11 16:20:00 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 PLUMBING | | | MUNICIPAL CODE CITY WPB | | | | | | 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN | | | DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3 | | | DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO | | | THE SANITARY DRAINAGE SYSTEM. | | | | | | 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC | | | UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION | | | 608. PLEASE INDICATE METHOD. | | | | | | 3. PLANS SHALL BE DESIGNED PER THE CURRENT CODE CYCLE | | | WHICH IS FBC-2007 W/2009 SUPPLEMENTS. PLEASE INDICATE | | | ON PLANS. SECTION 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|