| Notes |
| Date |
Text |
| 2009-05-15 14:23:32 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-4 SHOWS AN ALUMINUM STAND TO BE USED ON ROOF | | | FOR NEW CONDENSING UNIT. PROVIDE ENGINEERING AND | | | STRUCTURAL DETAIL FOR FIELD FABRICATED STAND SHOWING | | | WIND RESISTANCE CAPABILITIES AND MEANS OF ATTACHMENT TO | | | STRUCTURE IN ACCORDANCE WITH FBC-M 301.12. IF A | | | PRE-ENGINEERED A/C STAND IS USED, PROVIDE PRODUCT | | | APPROVAL WITH INSTALLATION INSTRUCTIONS PER FAC RULE | | | 9B-72. | | | | | | 2. PROVIDE APPLIANCE MANUFACTURER'S DATA SHOWING THE | | | CONDENSING UNIT IS DESIGNED FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBC-M 301.12. | | | | | | 3. AIR HANDLER SHALL BE PROVIDED WITH AUXILIARY DRAIN | | | PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3. | | | | | | 4. AHU MOUNTED SMOKE DETECTOR SHALL BE CONNECTED TO THE | | | BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBC-M | | | 606.4.1. | | | | | | 5. ALL NEW PIPING WHICH PENETRATES A RATED FLOOR OR | | | WALL ASSEMBLY SHALL BE PROTECTED AS A | | | THROUGH-PENETRATION IN ACCORANCE WITH FBC-B 712.3.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|