2009-05-15 14:23:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-4 SHOWS AN ALUMINUM STAND TO BE USED ON ROOF
 FOR NEW CONDENSING UNIT. PROVIDE ENGINEERING AND
 STRUCTURAL DETAIL FOR FIELD FABRICATED STAND SHOWING
 WIND RESISTANCE CAPABILITIES AND MEANS OF ATTACHMENT TO
 STRUCTURE IN ACCORDANCE WITH FBC-M 301.12. IF A
 PRE-ENGINEERED A/C STAND IS USED, PROVIDE PRODUCT
 APPROVAL WITH INSTALLATION INSTRUCTIONS PER FAC RULE
 9B-72.
  
 2. PROVIDE APPLIANCE MANUFACTURER'S DATA SHOWING THE
 CONDENSING UNIT IS DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 3. AIR HANDLER SHALL BE PROVIDED WITH AUXILIARY DRAIN
 PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3.
  
 4. AHU MOUNTED SMOKE DETECTOR SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBC-M
 606.4.1.
  
 5. ALL NEW PIPING WHICH PENETRATES A RATED FLOOR OR
 WALL ASSEMBLY SHALL BE PROTECTED AS A
 THROUGH-PENETRATION IN ACCORANCE WITH FBC-B 712.3.3.
  