Plan Review Notes For Permit 09050056
Permit Number 09050056
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-05-20 15:14:00*****DENIED*****
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED. ON SHEET E-101 IN SECTION F (CODES &
 STANDARDS), AMEND NFPA 101 TO REFLECT THE CURRENT
 EDITION.
  
 2. ON SHEET F/A-101, EXPLAIN VERBAGE " USE THOSE THAN
 APPLY" IN THE FIRE ALARM SYSTEM LEGEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722