Plan Review Notes
Plan Review Notes For Permit 09050056
Permit Number 09050056
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-15 12:09:52**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 553.73 AS ALL PROJECTS SUBMITTED
 FOR PERMIT AFTER MARCH 1ST, 2009 SHALL BE UNDER THE
 FOLLOWING CODES.
 PLEASE SEE FAC 69A-60.004 AS NFPA-101 AND NFPA-1 2006
 EDITIONS WERE REVISED AND ADOPTED AS OF DECEMBER 31,
 2009.
 E101 INDICATES SOME OF THE OLDER CODES.
 PLEASE BE SURE PLANS STATE THE FOLLOWING:
  
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
  
 SOME OTHERS SUCH AS 2005 NFPA-70 ARE OK ALONG WITH 2003
 NFPA-75 AND 2002 NFPA-72
  
 2) NOTE: PLEASE SEE BUILDING REVIEW NOTES FOR RATINGS
 FOR WALLS NEED TO BE INDICATED. IN ORDER TO USE THE
 WIRING METHODS IN NEC 645, THE LOCATION SHALL MEET ALL
 ITEMS LISTED IN NEC 645.4 (1-5). IF ALL ITEMS ARE NOT
 PROVIDED THEN NO WIRING METHODS IN 645 ARE PERMITTED TO
 BE USED. THEN ALL WIRING SHALL BE DONE PER CHAPTERS
 1-4.
 PLEASE CONFIRM RATINGS.
  
 3) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AN D.1.3 AS
 ANY NEW LIGHTING CONTROLS SHALL MEET THE PRESCRIPTIVE
 REQUIREMENTS FOR NEW BEING INSTALLED.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B.5.1,
 13-415.B.1 FOR LIGHTING PERFORMANCE CALCULATIONS FOR
 PRESCRIPTIVE SPACE REQUIREMENTS.
  
 5) NOTE: PLEASE SHOW ALL LISTED WALL AND PENETRATION
 DETAILS PER 300.21.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  