| Date |
Text |
| 2009-05-15 12:09:52 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE FS 553.73 AS ALL PROJECTS SUBMITTED |
| | FOR PERMIT AFTER MARCH 1ST, 2009 SHALL BE UNDER THE |
| | FOLLOWING CODES. |
| | PLEASE SEE FAC 69A-60.004 AS NFPA-101 AND NFPA-1 2006 |
| | EDITIONS WERE REVISED AND ADOPTED AS OF DECEMBER 31, |
| | 2009. |
| | E101 INDICATES SOME OF THE OLDER CODES. |
| | PLEASE BE SURE PLANS STATE THE FOLLOWING: |
| | |
| | 2007 FBC W/2009 REVISIONS. |
| | 2006 NFPA-101 |
| | |
| | SOME OTHERS SUCH AS 2005 NFPA-70 ARE OK ALONG WITH 2003 |
| | NFPA-75 AND 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE BUILDING REVIEW NOTES FOR RATINGS |
| | FOR WALLS NEED TO BE INDICATED. IN ORDER TO USE THE |
| | WIRING METHODS IN NEC 645, THE LOCATION SHALL MEET ALL |
| | ITEMS LISTED IN NEC 645.4 (1-5). IF ALL ITEMS ARE NOT |
| | PROVIDED THEN NO WIRING METHODS IN 645 ARE PERMITTED TO |
| | BE USED. THEN ALL WIRING SHALL BE DONE PER CHAPTERS |
| | 1-4. |
| | PLEASE CONFIRM RATINGS. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AN D.1.3 AS |
| | ANY NEW LIGHTING CONTROLS SHALL MEET THE PRESCRIPTIVE |
| | REQUIREMENTS FOR NEW BEING INSTALLED. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B.5.1, |
| | 13-415.B.1 FOR LIGHTING PERFORMANCE CALCULATIONS FOR |
| | PRESCRIPTIVE SPACE REQUIREMENTS. |
| | |
| | 5) NOTE: PLEASE SHOW ALL LISTED WALL AND PENETRATION |
| | DETAILS PER 300.21. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |