| 2009-05-14 14:18:05 | BUILDING PLAN REVIEW |
| | PERMIT: 09050056 |
| | ADD: 205 N DIXIE HWY |
| | CONT: M.A.C. CONSTRUCTION, INC |
| | TEL: (786) 236-1006 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 & 2007 FLORIDA EXISTING BUILDING |
| | CODE WITH |
| | 2009 SUPPLEMENTS. PLEASE PROVIDE LEVEL OF ALTERATION. |
| | 2007 EXISTING BUILDING CODE 401.4 A DESIGN PROFESSIONAL |
| | OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS |
| | OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF |
| | THIS CODE. PLEASE UPDATE YOUR CODE REFRENECES. |
| | |
| | 2) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5, |
| | TABLE 503, CHAPTER 6,& TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | 3) PLANS FAIL TO PROVIDE MANUFACTURERS INFORMATION FOR |
| | FLOOR LOADING, TABLE 1607.1 COMPUTER ROOMS SHALL BE |
| | DESIGNED FOR HEAVIER LOADS BASED ON THE ANTICIPATED |
| | OCCUPANCY. |
| | PLEASE PROVIDE FLOOR LOADING FOR THE RAISED FLOOR |
| | LOADING AS WELL AS THE STRUCTURAL SLAB. |
| | |
| | 4) PLANS INDICATE THE USAGE OF THIS ROOM TO BE A IT |
| | ROOM, NFPA 75 AND NEC 645.2 BOTH REQUIRE RATED WALLS. |
| | PLANS DO NOT INDICATE ANY RATING OF THE WALLS OR |
| | THROUGH PENETRATIONS. 712.3.1 THROUGH PENRTRATIONS. |
| | |
| | 5) SHEET A-1 INDICATES A PAIR OF NEW DOORS BUT NO |
| | RATING INFORMATION, OPENING PROTECTIVES TABLE 715.3. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |