2009-05-14 14:18:05BUILDING PLAN REVIEW
 PERMIT: 09050056
 ADD: 205 N DIXIE HWY
 CONT: M.A.C. CONSTRUCTION, INC
 TEL: (786) 236-1006
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 & 2007 FLORIDA EXISTING BUILDING
 CODE WITH
 2009 SUPPLEMENTS. PLEASE PROVIDE LEVEL OF ALTERATION.
 2007 EXISTING BUILDING CODE 401.4 A DESIGN PROFESSIONAL
 OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE. PLEASE UPDATE YOUR CODE REFRENECES.
  
 2) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503, CHAPTER 6,& TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 3) PLANS FAIL TO PROVIDE MANUFACTURERS INFORMATION FOR
 FLOOR LOADING, TABLE 1607.1 COMPUTER ROOMS SHALL BE
 DESIGNED FOR HEAVIER LOADS BASED ON THE ANTICIPATED
 OCCUPANCY.
 PLEASE PROVIDE FLOOR LOADING FOR THE RAISED FLOOR
 LOADING AS WELL AS THE STRUCTURAL SLAB.
  
 4) PLANS INDICATE THE USAGE OF THIS ROOM TO BE A IT
 ROOM, NFPA 75 AND NEC 645.2 BOTH REQUIRE RATED WALLS.
 PLANS DO NOT INDICATE ANY RATING OF THE WALLS OR
 THROUGH PENETRATIONS. 712.3.1 THROUGH PENRTRATIONS.
  
 5) SHEET A-1 INDICATES A PAIR OF NEW DOORS BUT NO
 RATING INFORMATION, OPENING PROTECTIVES TABLE 715.3.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved