| 2009-05-06 16:23:03 | **DENIED PLANS** |
| | |
| | |
| | |
| | 1) NOTE: PLANS WILL BE ROUTED TO ADDRESSING REVIEWER. |
| | THIS LOCATION AND PARKING LOT AREA NEEDS TO BE UNDER A |
| | SEPARATE ADDRESS FROM THE OTHER APPLIED BUS-STOP |
| | LOCATIONS. |
| | AN ADDRESS EXTENSION WILL BE DETERMINED. ONCE THIS IS |
| | DONE PLEASE BE SURE TO REVISE PLANS ACCORDINGLY. |
| | FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLANS INDICATE THE ELECTRICAL BEING FED FROM A |
| | SEPARATE PROPERTY WHICH IS A COMPLETELY SEPARATE LEGAL |
| | OWNER AND SEPARATE LEGAL PROPERTY. THIS IS NOT |
| | PERMITTED. PLEASE CONTACT YOUR LOCAL LEGAL |
| | REPRESENTATIVE ALONG WITH THE CITY ATTORNEY FOR |
| | SPECIFIC LEGAL QUESTIONS. |
| | |
| | A SEPARATE ELECTRICAL SERVICE SUCH AS METER ON A |
| | FREE-STANDING RACK OR BEING FROM EXISTING PALM BEACH |
| | COUNTY ELECTRICAL ON THE SAME PROPERTY MAY BE AN |
| | OPTION. |
| | PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| | GROUND FOR ALL LIGHTING FIXTURES/POLES, SERVICE, |
| | FEEDERS, CONDUCTORS, OVER CURRENT PROTECTION ETC. |
| | CONTINUOUS |
| | 215.5,230.70,230.71, 220,240, 310.16,ETC |
| | |
| | 3) NOTE: PLEASE REVISE TITLE BLOCKS FOR ENGINEERING |
| | FIRM TO COORDINATE WITH DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. (DBPR). THE STATE WEBSITE |
| | LISTS ALL ADDRESSING ASSOCIATED WITH AECOM USA INC |
| | LOCATED IN NEW YORK. |
| | PLEASE REVISE. |
| | 61G15-23.002, FS 471.023 |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |