2009-05-11 15:10:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE REFERENCE THE CURRENT CODE IN EFFECT AT TIME
 OF PERMIT APPLICATION. THE 2007 FLORIDA BUILDING CODE
 WITH 2009 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009.
  
 2. ENERGY CALCULATIONS: FORM 600C-04 WAS SUBMITTED FOR
 ENERGY CODE COMPLIANCE. THIS FORM IS NO LONGER
 APPLICABLE AS OF MARCH 1, 2009. ADDITIONS TO EXISTING
 RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW BUILDING
 CONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS OF
 EITHER METHOD A OR B AS APPLICABLE IN ACCORDANCE WITH
 FBC-R SECTION N1100.0.3. PLEASE SUBMIT FORM 100A-08 OR
 FORM 1100B-08 TO DEMONSTRATE ENERGY CODE COMPLIANCE.
  
 3. A COOLING AND HEATING LOAD CALCULATION SHALL BE
 PERFORMED ON THE BUILDING AND SHALL BE ATTACHED TO THE
 FORM 1100 SUBMITTED WHEN APPLICATION IS MADE FOR A
 BUILDING PERMIT IN ACCORDANCE WITH FBC-R SECTION
 N1107.AB.1.
  
 4. PLEASE PROVIDE ALL FLEXIBLE AND RECTANGULAR DUCT
 SIZES ON PLANS. DUCT SYSTEMS SERVING HEATING, COOLING
 AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN
 ACCORDANCE WITH THE PROVISIONS OF ACCA MANUAL D OR
 OTHER APPROVED METHODS PER FBC-R SECTION M1601.1.
  
 5. PAGE MEP-1 SHOWS NEW BATH EXHAUST TERMINATING AT THE
 SOFFIT. THE AIR REMOVED BY THE MECHANICAL EXHAUST
 SYSTEM SHALL BE DISCHARGED TO THE OUTDOORS AND SHALL
 NOT BE EXHAUSTED INTO A SOFFIT IN ACCORDANCE WITH FBC-R
 SECTION M1501.1.
  