| 2009-05-18 11:13:19 | BUILDING PLAN REVIEW |
| | PERMIT: 09050005 |
| | ADD: 308 COLONIEL RD |
| | CONT: UNDERHILL BLDG & ROOFING |
| | TEL: (561)379-3665 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009, 2007 FLORIDA EXISTING BUILDING CODE |
| | WITH 2009 SUPPLEMENTS, CHAPTER 10 ADDITIONS. PLEASE |
| | UPDATE PLANS. |
| | |
| | 2) SHEET A-2 INDICATES THE WIND DESIGN BUT NOT THE |
| | REFRENECE STANDARD USED? SEE DESIGN CRITERIA R301.2.1.1 |
| | |
| | 3) SHEET A-2 DOES NOT INDICATE ROOF VENTING EAVE NOT |
| | THE REQUIRED 50% A MINIMUM OF 3'-0" ABOVE THE EAVE |
| | VENTS. R806.2 |
| | |
| | 4) PLANS DO NOT PROVIDE A TRUE SECTION THROUGH THE WALL |
| | SECTION, WALL SECTION INDICATES IT TO BE A TYPICAL |
| | GARAGE WALL WHEREAS THIS IS A BEDROOM WITH TRAY |
| | CEILING. THE SECOND ISSUE IS THERE IS NO SECTION |
| | INDICATING A SECTION THROUGH THE GABLE END WALL, HOW |
| | THIS WALL WILL BE FRAMED? BRACING FOR THE GABLE END |
| | WALL, NOR HOW THE HORIZONTAL END JOINTS OF THE T-111 |
| | SIDING WILL BE TREATED. R 703..3.1. |
| | |
| | 5) BUILDING PROVISO: PROVIDE TRUSS BRACING FOR GABLE |
| | END WALL. R502.1.3.2 BRACING. TRUSSES SHALL BE BRACED |
| | TO PREVENT ROTATION AND PROVIDE LATERAL STABILITY IN |
| | ACCORDANCE WITH THE REQUIREMENTS SPECIFIED IN THE |
| | CONSTRUCTION DOCUMENTS FOR THE BUILDING AND ON THE |
| | INDIVIDUAL TRUSS DESIGN DRAWINGS. IN THE ABSENCE OF |
| | SPECIFIC BRACING REQUIREMENTS, TRUSSES SHALL BE BRACED |
| | IN ACCORDANCE WITH TPI/WTCA BCSI. |
| | |
| | 6) MEP-1 SMOKE ALRMS DUE NOT APPEAR IN THIS SHEET, |
| | R313.2 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS: |
| | |
| | 1. IN EACH SLEEPING ROOM. |
| | |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND |
| | UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS |
| | WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR |
| | BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON |
| | THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER |
| | LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE |
| | FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS SHALL BE |
| | INTERCONNECTED AND HARD WIRED. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. INTERCONNECTION AND HARD-WIRING OF SMOKE ALARMS IN |
| | EXISTING AREAS SHALL NOT BE REQUIRED WHERE THE |
| | ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF |
| | INTERIOR WALL OR CEILING FINISHES EXPOSING THE |
| | STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR |
| | BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD |
| | WIRING AND INTERCONNECTION WITHOUT THE REMOVAL OF |
| | INTERIOR FINISHES. |
| | |
| | 2. WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS, |
| | SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, OR THE |
| | ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE |
| | ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | R313.3 POWER SOURCE. IN NEW CONSTRUCTION, THE REQUIRED |
| | SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE |
| | BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM A |
| | COMMERCIAL SOURCE, AND WHEN PRIMARY POWER IS |
| | INTERRUPTED, SHALL RECEIVE POWER FROM A BATTERY. WIRING |
| | SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH |
| | OTHER THAN THOSE REQUIRED FOR OVERCURRENT PROTECTION. |
| | SMOKE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED |
| | WHEN INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER OR |
| | IN BUILDINGS THAT UNDERGO ALTERATIONS, REPAIRS OR |
| | ADDITIONS REGULATED BY SECTION R313.2.1. |
| | |
| | 7) |