Plan Review Notes
Plan Review Notes For Permit 09050005
Permit Number 09050005
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-15 15:29:58**DENIED REVIEW **
  
 1) NOTE: PLANS SHALL STATE MINIMUM CODE UNDER PERMIT
 APPLICATION MADE.
 ALL PLANS AFTER MARCH 1ST, 2009 SHALL CONTAIN THE
 FOLLOWING AT A MINIMUM FOR THIS SCOPE.
 2007 FBC W/ 2009 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE R313 FOR REQUIRED SMOKE ALARMS.
 THIS REQUIRES NEW/EXISTING TO MEET CURRENT CODE
 REQUIREMENTS. PLEASE ALSO SEE NFPA-72 11.5.1 AND
 11.8.3.
 THIS REQUIRES NEW SMOKE ALARM DEVICES INSIDE AND OUT
 NEW SLEEPING ROOM. SECTION 118.3 REQUIRED UNIT TO BE
 WITHIN 3FT OF THE HIGHEST POINT ON A SLOPED CEILING.
 ** KEEP IN MIND UNDER THE REVISED CODE IN 2002 AND 2005
 ALL OUTLETS IN BEDROOM REQUIRE AFCI PROTECTION
 INCLUDING SMOKE ALARM DEVICES.
  
 3) NOTE: PLANS NEED TO SHOW LOCATION OF NEW SERVICE
 MAINS AND DISCONNECTS.
 240.24, 110.26.
 BASED ON THE PLANS THE EXISTING PANEL DOES NOT MEET
 110.26 AND POWER WILL NOT BE RELEASED BACK TO DWELLING
 UNLESS RE-LOCATED.
  
 4) NOTE: PLEASE SEE 210.52D FOR BATH COUNTER GFI
 RECEPTACLE. THE GFI AS SHOWN NEEDS TO BE RELOCATED OR A
 NEW ONE ADDED. THIS IS TO PREVENT THE OCCUPANT FROM
 CROSSING OVER THE SINK AREA TO PLUG IN ANY APPLIANCE.
 THIS IS A SAFETY ISSUE.
  
 5) NOTE: PLEASE SEE THE RISER DOES NOT INDICATE ANY
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT FROM THE NEW MAIN TO THE EXISTING PANEL *A*.
 250.122,250.110,250.24.
  
 6) NOTE: PLEASE SEE RISER AS IT DOES INDICATE THE AIC
 RATING FOR THE OTHER NEW MAIN FEEDING EXISTING PANEL.
 110.9
  
 7) NOTE: *** PLEASE VERIFY WITH THE SERVICE PROVIDER
 THAT THEY ARE ACTUALLY GOING TO BE INSTALLING THE
 CONDUCTORS UNDERGROUND FROM THE POLE TO THE NEW
 SERVICE. THE RISER SHOWS TWO RUNS OF CONDUITS. MOST
 LIKELY FPL WILL NOT BE RUNNING PARALLEL SERVICE
 ENTRANCE CONDUCTORS. PLEASE ALSO VERIFY THEY WILL NOT
 BE INSTALLING A NEW HAND HOLE AT THE BASE OF POLE
 REQUIRING OWNER TO RUN FROM THAT LOCATION TO THE
 DWELLING. THIS IS BEING DONE IN MANY LOCATIONS FOR NEW
 SERVICES IN WHICH FPL IS NOT INSTALLING CONDUCTORS UP
 TO THE DWELLING. IF THIS IS THE CASE THE CONDUITS AND
 CONDUCTORS WOULD FALL UNDER NEC AND 310.16, 310.15B6 AT
 A MINIMUM.
  
 8) NOTE: PLEASE SEE CLOSET AREA WHICH INDICATES A NEW
 220V RECEPTACLE PER THE SYMBOL LEGEND. BASED ON THE
 PLANS THIS APPEARS THIS IS BEING SHOWN FOR THE AHU.
 PLEASE SEE 440.11, 440.12, 422.31, 424.19AS A
 RECEPTACLE FOR CORD AND PLUG CONNECTION MAY NOT BE USED
 OR INSTALLED.
 THIS REQUIRES A DISCONNECT.
  
 9) NOTE: PLEASE SEE LOAD CALCULATIONS WHICH ARE NOT
 CLEAR ON ACTUAL KW OF AHU/ HEAT. SEE 10KW LOAD NOTED AT
 100% WHICH IS SHOWN IN THE CALCULATIONS AS 7.5KW?
 PLEASE SEE 220.83 AND 424.3B
  
 10) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE FOR NEW BEDROOM
 CIRCUITS. 210.12
  
 11) NOTE: PLEASE SEE 408.4 WHICH WAS REVISED IN THE
 2005 NEC WHICH REQUIRES THE PANEL SCHEDULE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF * GENERAL LTS, OR GENERAL
 RECEPTACLES* IS NOT PERMITTED. THESE WOULD BE NOTED AS
 * MASTER BEDRM LTS PR MASTER BEDRM RECEPTS* OR WORDS TO
 THAT AFFECT.
  
 12) NOTE: PLEASE SEE 220.52 AS THE LAUNDRY/WASHER LOADS
 ARE REQUIRED TO BE FIGURED AT 1500VA MINIMUM. PLANS
 INDICATE 800VA.
  
 13) NOTE: PLEASE IDENTIFY THE THREE-WAY SWITCH AT THE
 MASTER BEDROOM BACK DOOR WHICH IS NOT SHOWN GOING TO
 ANYTHING.
 NEC 2005, FBC 106.1.1 FOR CLARITY.
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  