| 2009-05-15 15:29:58 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS SHALL STATE MINIMUM CODE UNDER PERMIT |
| | APPLICATION MADE. |
| | ALL PLANS AFTER MARCH 1ST, 2009 SHALL CONTAIN THE |
| | FOLLOWING AT A MINIMUM FOR THIS SCOPE. |
| | 2007 FBC W/ 2009 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE R313 FOR REQUIRED SMOKE ALARMS. |
| | THIS REQUIRES NEW/EXISTING TO MEET CURRENT CODE |
| | REQUIREMENTS. PLEASE ALSO SEE NFPA-72 11.5.1 AND |
| | 11.8.3. |
| | THIS REQUIRES NEW SMOKE ALARM DEVICES INSIDE AND OUT |
| | NEW SLEEPING ROOM. SECTION 118.3 REQUIRED UNIT TO BE |
| | WITHIN 3FT OF THE HIGHEST POINT ON A SLOPED CEILING. |
| | ** KEEP IN MIND UNDER THE REVISED CODE IN 2002 AND 2005 |
| | ALL OUTLETS IN BEDROOM REQUIRE AFCI PROTECTION |
| | INCLUDING SMOKE ALARM DEVICES. |
| | |
| | 3) NOTE: PLANS NEED TO SHOW LOCATION OF NEW SERVICE |
| | MAINS AND DISCONNECTS. |
| | 240.24, 110.26. |
| | BASED ON THE PLANS THE EXISTING PANEL DOES NOT MEET |
| | 110.26 AND POWER WILL NOT BE RELEASED BACK TO DWELLING |
| | UNLESS RE-LOCATED. |
| | |
| | 4) NOTE: PLEASE SEE 210.52D FOR BATH COUNTER GFI |
| | RECEPTACLE. THE GFI AS SHOWN NEEDS TO BE RELOCATED OR A |
| | NEW ONE ADDED. THIS IS TO PREVENT THE OCCUPANT FROM |
| | CROSSING OVER THE SINK AREA TO PLUG IN ANY APPLIANCE. |
| | THIS IS A SAFETY ISSUE. |
| | |
| | 5) NOTE: PLEASE SEE THE RISER DOES NOT INDICATE ANY |
| | EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF |
| | DISCONNECT FROM THE NEW MAIN TO THE EXISTING PANEL *A*. |
| | 250.122,250.110,250.24. |
| | |
| | 6) NOTE: PLEASE SEE RISER AS IT DOES INDICATE THE AIC |
| | RATING FOR THE OTHER NEW MAIN FEEDING EXISTING PANEL. |
| | 110.9 |
| | |
| | 7) NOTE: *** PLEASE VERIFY WITH THE SERVICE PROVIDER |
| | THAT THEY ARE ACTUALLY GOING TO BE INSTALLING THE |
| | CONDUCTORS UNDERGROUND FROM THE POLE TO THE NEW |
| | SERVICE. THE RISER SHOWS TWO RUNS OF CONDUITS. MOST |
| | LIKELY FPL WILL NOT BE RUNNING PARALLEL SERVICE |
| | ENTRANCE CONDUCTORS. PLEASE ALSO VERIFY THEY WILL NOT |
| | BE INSTALLING A NEW HAND HOLE AT THE BASE OF POLE |
| | REQUIRING OWNER TO RUN FROM THAT LOCATION TO THE |
| | DWELLING. THIS IS BEING DONE IN MANY LOCATIONS FOR NEW |
| | SERVICES IN WHICH FPL IS NOT INSTALLING CONDUCTORS UP |
| | TO THE DWELLING. IF THIS IS THE CASE THE CONDUITS AND |
| | CONDUCTORS WOULD FALL UNDER NEC AND 310.16, 310.15B6 AT |
| | A MINIMUM. |
| | |
| | 8) NOTE: PLEASE SEE CLOSET AREA WHICH INDICATES A NEW |
| | 220V RECEPTACLE PER THE SYMBOL LEGEND. BASED ON THE |
| | PLANS THIS APPEARS THIS IS BEING SHOWN FOR THE AHU. |
| | PLEASE SEE 440.11, 440.12, 422.31, 424.19AS A |
| | RECEPTACLE FOR CORD AND PLUG CONNECTION MAY NOT BE USED |
| | OR INSTALLED. |
| | THIS REQUIRES A DISCONNECT. |
| | |
| | 9) NOTE: PLEASE SEE LOAD CALCULATIONS WHICH ARE NOT |
| | CLEAR ON ACTUAL KW OF AHU/ HEAT. SEE 10KW LOAD NOTED AT |
| | 100% WHICH IS SHOWN IN THE CALCULATIONS AS 7.5KW? |
| | PLEASE SEE 220.83 AND 424.3B |
| | |
| | 10) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS ON THE PANEL SCHEDULE FOR NEW BEDROOM |
| | CIRCUITS. 210.12 |
| | |
| | 11) NOTE: PLEASE SEE 408.4 WHICH WAS REVISED IN THE |
| | 2005 NEC WHICH REQUIRES THE PANEL SCHEDULE TO BE |
| | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE THE USE OF * GENERAL LTS, OR GENERAL |
| | RECEPTACLES* IS NOT PERMITTED. THESE WOULD BE NOTED AS |
| | * MASTER BEDRM LTS PR MASTER BEDRM RECEPTS* OR WORDS TO |
| | THAT AFFECT. |
| | |
| | 12) NOTE: PLEASE SEE 220.52 AS THE LAUNDRY/WASHER LOADS |
| | ARE REQUIRED TO BE FIGURED AT 1500VA MINIMUM. PLANS |
| | INDICATE 800VA. |
| | |
| | 13) NOTE: PLEASE IDENTIFY THE THREE-WAY SWITCH AT THE |
| | MASTER BEDROOM BACK DOOR WHICH IS NOT SHOWN GOING TO |
| | ANYTHING. |
| | NEC 2005, FBC 106.1.1 FOR CLARITY. |
| | |
| | |
| | |
| | * IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |