| Plan Review Notes For Permit 09040660 |
| Permit Number |
09040660 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-07 12:02:37 | ****CORRECTIONS**** | | | ****REVISED 5/11**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE CLARIFY, HOW HAS "ENCLOSED" CONDITION BEEN | | | DETERMINED? SOME, BUT APPARENTLY NOT ALL, UNITS HAVE | | | OPENING PROTECTION. | | | | | | IT IS POSSIBLE THAT THIS ISSUE MAY BE ADDRESSED BY | | | TELEPHONE. ALTERNATIVELY, PRESSURES CAN BE CALCULATED | | | USING "PARTIALLY ENCLOSED" CONDITION. | | | | | | 2. PLEASE NOTE THAT ISSUES REGARDING NOC MUST BE | | | RESOLVED PRIOR TO FIRST INSPECTION FS713. | | | | | | | | | HAD A CONVERSATION W/CONTR ON 5/11 - | | | | | | 1. "ENCLOSED" MAY BE EVIDENCED BY EITHER: | | | | | | ENGINEER PROVIDE CALCULATIONS TO SHOW HOW HE'S ARRIVED | | | AT "ENCLOSED" CONDITION | | | | | | CONTRACTOR TO PROVIDE PERMIT NUMBERS AND CALCULATIONS | | | TO SHOW THAT ENOUGH UNITS IN THE BUILDING ARE PROTECTED | | | TO JUSTIFY "ENCLOSED" CONDITION | | | | | | CONTRACTOR MAY PROPOSE ALTERNATE (HIGHER) DESIGN | | | PRESSURE, SO ENGINEERING WOULD NOT BE REQUIRED BUT A | | | CODE COMPLIANT JOB WOULD BE PROVIDED | | | | | | ANY OTHER RESOLUTION THAT THE CONTRACTOR PROPOSES WILL | | | BE CONSIDERED. | | | | | | 2. REGARDING NOC, CONDO ASSOCIATION CAN SIGN (BECAUSE | | | OUTSIDE OF BUILDING IS OWNED BY CONDO ASSOC, NOT | | | HOMEOWNER) | | | |
|