| 2009-05-19 09:58:23 | DENIED BY BUILDING |
| | |
| | 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CALCULATION FORM. FBC 13-103.1.2 |
| | |
| | 2) THE ENERGY CALCULATIONS DO NOT LIST THE INSULATION |
| | FOR THE SECOND FLOOR WOOD FRAME WALLS. PLEASE REVISE |
| | PLANS OR CALCULATIONS TO CORRESPOND. FBC 13-600 |
| | |
| | 3) SPECIFY THE MANUFACTURER AND TRUSS ANCHOR FOR THE |
| | ADDITIONAL STRAPPING ON THE PLANS. R802.1.6.5 |
| | |
| | 4) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING |
| | FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE |
| | FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 |
| | INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. WHERE ROOF FRAMING WITH A |
| | SPECIFIC GRAVITY, 0.42< G < 0.49 IS USED, SPACING OF |
| | RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| | NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND |
| | SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. |
| | |
| | 5) THE AGGREGATE AREA OF REPLACED GLAZING EXCEEDS 25 |
| | PERCENT OF THE TOTAL AREA OF GLAZED OPENINGS IN THE |
| | DWELLING. SHOW COMPLIANCE WITH FBC EB 606.4 REPLACEMENT |
| | OF WINDOWS AND DOORS. THE REPLACEMENT OF GARAGE DOORS, |
| | EXTERIOR DOORS, SKYLIGHTS, OPERATIVE AND INOPERATIVE |
| | WINDOWS SHALL BE DESIGNED AND CONSTRUCTED TO COMPLY |
| | WITH CHAPTER 16 OF THE FLORIDA BUILDING CODE, BUILDING |
| | . |
| | EXCEPTIONS: |
| | 1. OPENING PROTECTION EXCEPTION: FOR ONE- AND |
| | TWO-FAMILY DWELLINGS CONSTRUCTED UNDER CODES OTHER THAN |
| | THE FLORIDA BUILDING CODE AND LOCATED IN WIND-BORNE |
| | DEBRIS REGIONS, THE REPLACEMENT OF GARAGE DOORS AND |
| | EXTERIOR DOORS WITH GLAZING, SLIDING GLASS DOORS, GLASS |
| | PATIO DOORS, SKYLIGHTS AND OPERABLE AND INOPERABLE |
| | WINDOWS WITHIN ANY 12-MONTH PERIOD SHALL NOT BE |
| | REQUIRED TO HAVE OPENING PROTECTION BUT SHALL BE |
| | DESIGNED FOR WIND PRESSURES FOR ENCLOSED BUILDINGS, |
| | PROVIDED THE AGGREGATE AREA OF THE GLAZING IN THE |
| | REPLACED COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE |
| | AGGREGATE AREA OF THE GLAZED OPENINGS IN THE DWELLING |
| | OR DWELLING UNIT. SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS AND INSTALLATION SCHEDULES FOR THE STORM |
| | PANELS. SEE SAMPLE SCHEDULE ATTACHED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |