| 2009-07-03 09:47:17 | *** TEMP FAILED, UNTIL ORIGINAL APPLICATION IS | | | SUBMITTED. ONLY A COLOR COPY OF THE FRONT OF THE | | | ORIGINAL APPLICATION WAS BROUGHT BACK. CALLED AND LEFT | | | MESSAGE FOR MIKE FROM KAST CONSTRUCTION. | | 2009-07-03 09:45:50 | NOTE: PLEASE SHOW LIGHTING PER NFPA-101 7.8, | | | 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN FOR | | | MINIMUM EGRESS LIGHTING. | | | ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE | | | OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER | | | EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR | | | LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS | | | COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS. | | | PLEASE BE SURE TO GO OVER THIS WITH BUILDING | | | OWNER/MANAGEMENT. | | | OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED | | | UNDER EMERGENCY POWER OR PROVIDE THE TWO FIXTURES ON EM | | | CIRCUIT WITH BATTERY BACK UP. | | | |
|