| 2009-05-15 09:28:20 | **DENIED REVIEW ** |
| | |
| | 1) NOTE: THE MINIMUM CODES UNDER DESIGN AS ADOPTED |
| | MARCH 1ST 2009 SHALL BE AS FOLLOWS. THE ELECTRICAL CODE |
| | NFPA-70 WAS REVISED ON DECEMBER 8TH, 2006. THE PLANS |
| | STILL INDICATE THE 2002 NEC. PLEASE ALSO SEE FAC |
| | 69A-60.004 WHICH ADOPTED THE NEW NFPA-101 2006 EDITION |
| | AS OF DECEMBER 31, 2008. |
| | PLEASE ADJUST AND DESIGN TO THESE CODES. |
| | |
| | 2007 FBC W/ 2009 SUPPLEMENTS. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES NEED |
| | TO BE DONE UNDER THE NEW CODE. PLEASE SEE 2007 FBC WITH |
| | 2009 REVISIONS. THE CODE SECTION IS MINOR AS THE TABLE |
| | DID CHANGE. |
| | THE LPD AS SHOWN LOOKS LIKE IT EXCEEDS ALLOWANCES BASED |
| | ON ACTUAL SQ FOOTAGE ON PLANS FOR SPACE. IT IS NOT |
| | PERMITTED TO INCLUDE WALL AREAS WHERE SHAFTS ETC ARE |
| | LOCATED. |
| | APPLICATION HAS THE SQ FT CLOSER TO ACTUAL WHICH STATES |
| | 595. |
| | |
| | ** SOME OF THESE ITEMS COULD HAVE BEEN REDLINED HOWEVER |
| | WE DO NOT HAVE THE AUTHORITY TO REVISE DESIGNS ON |
| | PLANS. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |