2009-05-08 10:40:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. RETURN TRANSFER DUCTS AT BACK LEFT AND BACK RIGHT
 BEDROOMS US TOO SMALL TO MEET THE BALANCED RETURN AIR
 REQUIREMENTS. TRANSFER DUCTS SHALL INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE SQUARE
 INCHES OF THE SUPPLY DUCT ENTERING THE ROOM IT'S
 SERVING AND THE DOOR HAVING AT LEAST AN UNRESTRICTED 1
 INCH UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE IN
 ACCORDANCE WITH FBC-R SECTION M1602.4 EXCEPTION 1.
  
 2. RETURN AIR TRANSFER DUCT FOR MASTER BEDROOM HAS NO
 SIZE SHOWN ON PLANS. PLEASE SHOW DUCT SIZE ON PLANS TO
 DEMONSTRATE COMPLIANCE WITH FBC-R SECTION M1602.4
 EXCEPTIONS 1 AND 3.
  
 3. AHU DETAIL CALLS FOR THE PRIMARY DRAIN LINE TO BE
 ROUTED TO AN "OVERFLOW DRAIN." PLEASE CLARIFY THIS
 DESIGN. CONDENSATE FROM THE COOLING COIL SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL (OUTDOORS, PERVIOUS AREA, MIN. 12" FROM THE
 HOUSE AND 6" ABOVE GRADE). CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS WHERE IT
 WOULD CAUSE A NUISANCE IN ACCORDANCE WITH FBC-R SECTION
 M1411.3.
  
 4. A FORM 1100C-07 ENERGY CALCULATION WAS SUBMITTED.
 THIS FORM IS NOT VALID. THE 2009 SUPPLEMENT TO THE 2007
 FLORIDA BUILDING CODE IS IN EFFECT AS OF MARCH 1, 2009.
 THE CORRECT FORM IS 1100B-08 IN ACCORDANCE WITH THE
 2009 SUPPLEMENT. PLEASE SUBMIT THE CORRECT FORM. FOR
 MORE INFORMATION ON THE 2009 SUPPLEMENT TO THE 2007
 FLORIDA BUILDING CODE, PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  