| Plan Review Notes For Permit 09040613 |
| Permit Number |
09040613 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-05-07 15:01:29 | 1. FBC 2007 EXISTING BUILDINGS VOLUME - 404.1, 404.2 , | | | 612.1, 711.1: PROVIDE ENERGY CALCULATIONS FOR THIS | | | RECONFIGURATION OF AN EXISTING SPACE | | | 2. FBC 2007 13-415.ABC.1.1, 13-415.ABC.1.2 - NO | | | OCCUPANCY SENSORS APPEAR TO HAVE BEEN PROVIDED FOR THE | | | SECOND FLOOR AREA. | | | 3. FBC 2007 13-415.B.1 - IT APPEARS THAT METHOD "B" HAS | | | BEEN UTILIZED TO DEMONSTRATE COMPLIANCE, HOWEVER | | | APPROXIMATELY 2000 SQUARE FEET OF AREA HAS NOT BEEN | | | INCLUDED IN THE TABULAR DATA PROVIDED. |
|