| 2009-05-11 09:21:21 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. NO ENERGY CALCULATIONS OR COOLING LOAD CALCULATIONS |
| | WERE PROVIDED FOR REVIEW. ADDITIONS TO EXISTING |
| | RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW BUILDING |
| | CONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS OF |
| | EITHER METHOD A OR B AS APPLICABLE IN ACCORDANCE WITH |
| | FBC-R SECTION N1100.0.3. SUBMIT THE APPROPRITAE FORM |
| | 1100A-08 OR FORM 1100B-08 AS REQUIRED BY THIS SECTION. |
| | |
| | 2. A COOLING AND HEATING LOAD CALCULATION SHALL BE |
| | PERFORMED ON THE BUILDING AND SHALL BE ATTACHED TO THE |
| | FORM 1100 SUBMITTED WHEN APPLICATION IS MADE FOR A |
| | BUILDING PERMIT IN ACCORDANCE WITH FBC-R SECTION |
| | N1107.AB.1. |
| | |
| | 3. PAGE M-1: PROPOSED BEDROOM #1 DOES NOT SHOW ANY |
| | PROVISIONS FOR BALANCED RETURN AIR. PROVISIONS SHALL BE |
| | MADE TO AVOID UNBALANCED AIR FLOWS AND PRESSURE |
| | DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR IN |
| | ACCORDANCE WITH FBC-R SECTION M1602.4. |
| | |
| | 4. PROVIDE AN EQUIPMENT SCHEDULE FOR ALL A/C EQUIPMENT |
| | AND EXHAUST FANS TO BE INSTALLED. THIS INFORMATION IS |
| | NEEDED TO CONFIRM COMPLIANCE WITH VENTILATION |
| | REQUIREMENTS AS STATED IN FBC-R SECTION M1507.3 AND |
| | CONFORMANCE WITH THE ENERGY AND COOLING LOAD |
| | CALCULATIONS AS STATED IN COMMENTS 1 AND 2 ABOVE. |
| | |